Master Programming Level
Programming
MS-5UD and MS-10UD Series Manual —
P/N 52626:B1 6/30/2009
99
3.5.5.4.3.4 Trouble Call Limit (Dialer Runaway Prevention)
The Call Limit option limits the number of DACT trouble calls to the Central Station, to a
programmed amount between 0 and 99, for each unique trouble within a 24 hour period.
Separate limit counters keep track of each unique type of trouble. Note that the number of
phone line (communication) faults called to the Central Station are not limited by this feature.
No subsequent restoral message is sent to the Central Station(s) for a particular trouble whose
call limit has been reached. Local DACT annunciation will still track the particular trouble and
restoral.
To set the Trouble Call Limit, press
3
while viewing Central Station Screen #2. The following
screen will be displayed.
Enter a value between 00 and 99, then press Enter to set the Call Limit to this value.
Note: Entering a value of 00 will disable the Trouble Call Limit allowing the DACT to call the
Central Station an unlimited number of times. This is the factory default setting.
3.5.5.4.4 Service Terminal
The FACP can be programmed remotely from a PC using a modem and telephone line.
Information can also be retrieved from the FACP using the same method. The Upload/
Download option allows an operator to set the necessary parameters to allow the uploading and
downloading of data between the FACP and PC. The Service Terminal selection provides the
means for entering these parameters.
Pressing
1
while viewing Onboard DACT Screen #2 will cause the following screens to appear:
CENTRAL STATION
1=PRIMARY
2=SECONDARY
3=CALL LIMIT
Central Station Screen #2
TROUBLE CALL LIMIT
RANGE 00-99 TROUBLES
*
Backup Reporting Screen
DACT
1=SERVICE TERMINAL
2=SUPERV PHONE LINE
Onboard DACT Screen #2
SERVICE TERMINAL
1=RING COUNT 0
Service Terminal Screen