ANN-BUS Devices
Installation
MS-5UD and MS-10UD Series Manual —
P/N 52626:B1 6/30/2009
43
The following table shows the ANN-80 connections to the MS-5UD/MS-10UD.
Programming
Following installation and wiring of the ANN-80 LCD annunciator to the FACP, the annunciator
must be added to the system via FACP programming. Refer to the programming section titled
"ANN-BUS" on page 80 in this manual for detailed programming information. Select the LCD
option for programming.
MS-5UD/MS-10UD (TB3)
ANN-80 (TB1)
Terminal 4 GND (-)
Terminal 1 (-)
Terminal 3 PWR (+)
Terminal 2 (+)
Terminal 2 A (ANN-BUS)
Terminal 3 (A)
Terminal 1 B (ANN-BUS)
Terminal 4 (B)
Figure 2.20 ANN-80 Wiring to FACP
FACP
ANN-80
ANN-BUS and power wiring are
supervised and power-limited
4 3 2 1
TB3