48
ES-200X Series Manual —
P/N LS10131-000FL-E:C 7/25/2018
Installation
Automatic Audio Panel Control
(1 of 5 using the legacy ACC panel) can be generated over the selected speaker circuit. Any fault in the ECC-50/100 audio system is sent
to the FACP via the FACP Data Bus and is indicated as an annunciator fault on the FACP display. A fault at the ACC-25/50ZS Series
panel will cause the FACP to indicate a System Trouble and the display will indicate a Voice Evac Fault.
For speaker circuit mapping and audio message assignment, refer to “Zone Message” on page 70. Also, refer to “Programmed Activa-
tion by FACP” in chapter 3 of the
ECC-50/100 Instruction Manual
(Doc. LS10001-000FL-E) or Appendix D, “Programmed Activation
by FACP” in the ACC-25/50ZS Series Instruction Manual (Doc. 51889).
Connect the ECC-50/100 panel’s FACP Data Bus at TB13 to TB9 on the ES-200X FACP.
The only connection between the FACP and ACC-25/50ZS Series audio panel is a pair of communication wires connected between the
A(+)/B(-) terminals on TB9 of the FACP and TB1 terminals 2 & 3 of the ACC-ZPMK module on the audio panel.
A B
Figure 2.32 FACP Connection to ECC-50/100 Series Audio Panel