40
ES-200X Series Manual —
P/N LS10131-000FL-E:C 7/25/2018
Installation
Optional Module Installation
Setting Printer Options
Refer to the documentation supplied with the PRN-7 printer for instructions on using the printer menu controls. Set the printer options
(under the menu area) as shown in the following table:
PRN-6F Printer Installation
When connected to the FACP via the ANN-S/PG module, the PRN-6F prints the status changes within the control panel and time-stamps
the printout with the time of day and date that the event occurred. It provides 80 columns of data on standard 9” x 11” tractor-feed paper.
This section contains information on connecting a printer to the control panel and setting the printer options.
Connecting PRN-6F Printer
Remote printers require a primary AC power source. If required for the fire alarm system configuration (for example, a Proprietary Fire
Alarm System), a remote printer requires a secondary power source (battery backup). Since a secondary power source is not provided as
a standard feature, a separate UL-listed Uninterruptible Power Supply (UPS) should be used. The building emergency power supply may
be used, as long as it meets the power continuity requirements of NFPA 72. Refer to NFPA 72 for further details.
Connect the remote printer to the FACP via the ANN-S/PG module using a standard DB-25 cable. One end of the cable will plug into the
DB-25 connector on the PRN printer and the other end plugs into the parallel connector on the ANN-S/PG module. Note that the 9-pin
DB-9 port on the ANN-S/PG is used to connect a serial printer. The 25-pin port is used for a Centronics parallel printer cable. Connect
either a serial or parallel printer, but not both at the same time.
Setting Printer Options
Refer to the documentation supplied with the PRN-6F printer for instructions on using the printer menu controls. Set the printer options
(under the menu area) as shown in the following table:
Option
Setting
Option
Setting
Font
HS Draft
CPI
10CPI
LPI
6 LPI
Skip
0.5
ESC Character
ESC
Emulate
LQ-2550
Bidirectional Copy
ON
I/O
CG-TAB
Graphic
Buffer
64K
Country
E-US ASCII
Serial
Auto CR
OFF
Baud
9600 or 2400
Color Option
Not Installed
Format
7 Bit, Even, 1 Stop
Formien
Protocol
XON/XOFF
Lines
6LPI=60
Character Set
Standard
Standard
Exec 10.5
SI.Zero
On
Barcode
Off
Auto LF
On
Barcode
Unsecured
Table 2.1 PRN-7 Setup Options
Option
Setting
Option
Setting
Font
HS Draft
CPI
10CPI
LPI
6 LPI
Skip
0.5
ESC Character
ESC
Emulate
Epson FX-850
Bidirectional Copy
ON
I/O
CG-TAB
Graphic
Buffer
40K
Country
E-US ASCII
Serial
Auto CR
OFF
Baud
9600 or 2400
Color Option
Not Installed
Format
7 Bit, Even, 1 Stop
Formien
Protocol
XON/XOFF
Lines
6LPI=60
Character Set
Standard
Standard
Exec 10.5
SI.Zero
On
Auto LF
On
PAPER
BIN 1
12/72”
BIN 2
12/72”
SINGLE
12/72”
PUSH TRA
12/72”
PULL TRA
12/72”
PAP ROLL
12/72”
Table 2.2 PRN -6 Setup Options