32
ES-200X Series Manual —
P/N LS10131-000FL-E:C 7/25/2018
Installation
Optional Module Installation
Before installing the module, place the disconnect switch to the right (disconnect) position to prevent accidental activation of the munic-
ipal box. Note that a Disconnect LED will illuminate after the module is installed in the ES-200X. In addition, the System Trouble LED
will turn on to indicate the Disconnect condition.
The following steps must be followed when installing the 4XTMF module:
1.
Remove all power (Primary and Secondary) from the FACP before installing 4XTMF.
2.
Carefully plug the connectors on the 4XTMF module into connectors J12 and J13 on the ES-200X main circuit board, being careful
not to bend any pins.
3.
Secure 4XTMF module to standoffs with supplied screws.
4.
Slide SW2 on the ES-200X main circuit board to the down position.
5.
Enable 4XTMF supervision in user programming. Refer to “4XTMF Supervision” on page 80.
6.
Reapply power to the FACP.
7.
For proper 4XTMF operation, the output relays must be programmed for the factory default settings: Alarm Relay 1, Trouble Relay
2 and Supervisory Relay 3.
8.
When the installation has been complete, enable the 4XTMF module by sliding the disconnect switch to the left.
9.
Test system for proper operation.
Figure 2.15 4XTMF Transmitter Module
Connect to FACP J12 & J13
Disconnect Switch
shown in
disconnect position
TBL Jumper
}
Remote Alarm (power-limited)*
}
Remote Trouble (power-limited)*
No connection
}
Municipal Box (nonpower-limited)*
1 2 3 4 5 6 7
+ - + - + -
Polarities are shown for module activation
Note: The 4XTMF Module is not directly suitable for transmitting a reverse polarity
supervisory signal. For applications using reverse polarity of a supervisory signal, refer to
“FACP with Keltron” on page 143.
* Wiring from these
terminals can exit the
protected premises.
Dummy load
terminals 6 and 7
(4.7k
Ω
, ¼ watt
resistor) if Municipal
Box is not connected.
Disconnect LED
4
x
tm
f.
w
m
f