ES-200X Series Manual —
P/N LS10131-000FL-E:C 7/25/2018
141
NFPA Standard-Specific Requirements
NFPA 72 Proprietary Protective Signaling Systems
Figure C.3 Proprietary Protective Signaling System
Form-C relay contact programmed
to activate on Supervisory condition.
Form-C Trouble contact which will
automatically activate on any Trouble condition.
Form-C Alarm contact programmed
to activate on General Alarm.
ES-200X Main Board
ES-200X
Addressable Fire Control Panel
Notes:
1. Connection between the ES-200X and the transmitter
are supervised by the transmitter.
2. This ES-200X/Transmitter arrangement can be
employed for NFPA 72 Proprietary Protective Signaling
System.
3. Potter Electric Model EFT-C has not been tested for UL
864 9th Edition and is for use in retrofit applicationsonly.