90
ES-200X Series Manual —
P/N LS10131-000FL-E:C 7/25/2018
Programming
Master Programming Level
3.6.8 Annunciators
Pressing
3
while viewing Programming Screen #3 will cause the control panel to display the following
screens:
A printer module, graphic annunciator module, LCD annunciator module, LED annunciator module, and relay module can be pro-
grammed into the ES-200X system. These devices communicate with the FACP over the ANN-BUS terminals on the control panel.
ANN-BUS Setup
Two ANN-BUS circuits are available on the ES-200X. Press
1
to configure the Primary ANN-BUS or press
2
to configure the Secondary ANN-BUS. The following screens will be displayed for either ANN-BUS cir-
cuit where
(XXX)
indicates either
Primary
or
Secondary
.
ANN-BUS Enabled
The ANN-BUS must be enabled if any modules are connected to the ANN-BUS terminals. To enable the ANN-BUS, press
1
while
viewing ANN-BUS screen #1 so that the display reads
ANN XXX Enabled Yes.
Each press of the
1
key will cause the display to toggle
between
ANN XXX Enabled Yes
and
ANN XXX Enabled No
.
Modules Installed
If an ANN-BUS module is installed, press
2
for
Modules Installed
to select ANN-BUS addresses for the
module(s). The only difference between the two programming screens are the addresses. The Primary Bus
module addresses will have a prefix of “1-” while the Secondary Bus module addresses will have a prefix
of “2-”. The following screen will be displayed for either bus circuit.
Pressing the down arrow key will allow the programmer to view additional screens displaying Addresses 1-8. To select one or more
addresses for the installed module(s), press the number key corresponding to the module address in each screen. The following screen
will be displayed for each address:
OFF_NORMAL_MESSAGE
308
000
000
LB
LX
24_HOUR_TEST
602
000
000
RP
24 HOUR ABNORMAL TES
608
000
000
RY
UPDOWN REQUEST
411
000
000
RB
UPLOAD SUCCESS
416
000
000
RS
DOWNLOAD SUCCESS
412
000
000
RS
UPDOWN FAILURE
413
000
000
RR
GENERAL ALARM
000
000
000
00
00
GENERAL SUPERVISORY
000
000
000
00
00
Table 3.3 Event Codes (Continued)
PROGRAMMING
1=HISTORY
2=COMMUNICATOR
3=ANNUNCIATORS
Programming Screen #3
ANN-BUS SELECT
1=PRIMARY
2=SECONDARY
3=ANN-BUS OPTIONS
ANNUNCIATORS
1=PRIMARY
2=SECONDARY
3=ANN-BUS OPTIONS
Annunciators Screen
ANN XXX
1=ENABLED NO
2=MODULES INSTALLED
3=AUTO-CONFIGURE
ANN-BUS Screen #1
ANN XXX
1=CLASS A NO
ANN-BUS Screen #2
ANN XXX
1=ENABLED NO
2=MODULES INSTALLED
3=AUTO-CONFIGURE
ANN XXX Screen #1
ANN-BUS MODULES
1=ADDR. X-1 NONE
2=ADDR. X-2 NONE
3=ADDR. X-3 NONE
ANN-BUS Modules Screen #1
ANN-BUS MODULE X-1
ANN-BUS ADDRESS
1=TYPE NONE
ANN-BUS Address Screen