TWINFLEX
®
SRP Remote Status Indicator Engineering and Commissioning Manual
16
SRP Control Panel Peripheral Bus Settings
To set up the SRP Control Panel to supervise the RSI(s) installed in the system, set the Write Enable
switch to ON position, login with Engineer level access, and select
“13 RSI SUPERVISION”
from the
MAIN MENU.
Then using the UP/DOWN and LEFT/RIGHT arrow keys, navigate to each relevant RSI
address and set the
MODE
to
On.
When this is done press ESC to return to the
SRP Control Panel’s MAIN MENU. The SRP Control
Panel will now be set up to supervise the selected RSI(s) and will report them as missing if there is a
cable break or loss of communications. Set the Write Enable switch back to OFF position.
NOTES
:
If an RSI address MODE is turned ON and the RSI is not connected to the Peripheral Bus, the
panel reports
an “RSI Missing” fault.
The RSI must be supervised to be fully functional. The Home Screen on the RSI indicates that
it is supervised by displaying a check mark next in the upper right corner of the display.
RSI Panel Settings
Setting RSI Address/Number
Each RSI has to be set with a unique address in the range 1
– 8, the default address is 1. This is done
using DIL switches A0 to A2.
NOTES:
The RSI must be reset or power cycled for changes to take effect.
The RSI address is indicated on the Home Screen in the upper right corner of the RSI display.
Address Settings
A0 (1)
A1 (2)
A2 (3)
RSI Address
Off
Off
Off
1
On
Off
Off
2
Off
On
Off
3
On
On
Off
4
Off
Off
On
5
On
Off
On
6
Off
On
On
7
On
On
On
8
RSI
Buzzer
The local RSI
internal buzzer can be switched off using DIL switch SP1 (4).
Buzzer Setting
SP1 (4)
Buzzer State
On
Buzzer on
Off
Buzzer off
This setting only affects the local buzzer state and has no effect on the panel buzzer or other RSIs on
the system.
NOTE:
The RSI must be reset or power cycled for changes to take effect.