TWINFLEX
®
SRP Remote Status Indicator Engineering and Commissioning Manual
17
LCD Contrast
LCD Contrast
The LCD contrast can be adjusted by rotating the screw on the variable resistor, located in the upper
right of the main RSI PCB.
Powering Up
Turn on the SRP Control Panel to initialize the RSI. The RSI briefly displays the start-up message:
When communication between the RSI and SRP Control Panel is established, the HOME screen shows
the same date and time as displayed on the SRP Control Panel:
NOTES:
The Time/Date format on the RSI is same as the SRP Control Panel.
The RSI displays the same Home Screen message as the SRP Control Panel (lines 2 and 3).
If the Home Screen is modified on the SRP Control Panel, the Home Screen on the RSI gets
updated automatically.
The RSI Access Level and Address is displayed in the upper right corner of the RSI display.
“NM” is NORMAL access and “US” is USER access, depending on the Enable Key Switch
position. The
“x” represents the RSI address with a value between 1 and 8.
A check mark appears next to the Access Level to indicate that the RSI is being supervised.
RSI INITIALIZED
WAITING FOR PANEL...
01/23/2016 04:56
√
NMx
TWINFLEX RELEASING
FIKE(UK)
Turn Key/Press Enter
Rotate anticlockwise to
reduce the contrast
(
lighten text
)
Rotate clockwise to
increase the contrast
(
darken text
)