End User Training
A Fire Alarm System is of little use if the end user and/or the responsible persons who will be present in
the building do not know how to operate and respond to the system. It is therefore essential that
commissioning includes training for the users of the system and responsible persons.
User instructions and a Zone Chart should be left adjacent to the SRP Control Panel. As access to the
system must be controlled by responsible persons, it would be unusual to display the access codes on
this notice. These codes must however be available for the responsible persons, so ensure that they
know and record them in a secure place.
The
TWINFLEX
®
SRP User Guide
should be explained and left with the responsible person on site, for
storage in an accessible and known location, in order that the responsible person and the service
engineer may keep information records up to date.
A single page user instruction sheet is included at the end of this manual. A copy of this should be
mounted adjacent to the Control Panel.
Maintenance
The RSI does not require user maintenance, however periodic functional checks should be carried out
by an engineer or responsible persons.
Technical Data
Remote Status Indicator Specification
Dimensions (mm)
250 x 140 x 85
Weight
650 grams
Construction
UL94-V0 rated ABS
Cable Entry
6 x 20mm knockouts, 4 x double 20mm knockouts
Cable type
2 core 1.5mm
2
screened fire rated cable
Operating voltage
Nominal 24V DC (Range 21 - 32V DC)
Operating current Quiescent @ 24V DC
15 mA (back light off)
Operating current Max @ 24V DC
35 mA (controls enabled, back light on)
Communications
Multi-drop RS-485
Total peripheral bus length
500m (max)
IP rating
30
Maximum number of RSI per Control Panel
8
Operating temperature
-5
O
C to 40
O
C, Class A