TWINFLEX
®
SRP Remote Status Indicator Engineering and Commissioning Manual
20
Fire Alarm Controls
The Silence Alarms button will silence any fire alarm sounders that are currently sounding.
The Reset System button will reset the SRP Control Panel and place the system into a non-alarm state.
The Sound Alarms button will activate all fire alarm sounders.
The Silence Buzzer button will silence the buzzer on the SRP Control Panel and all RSI panels.
System Controls
SELECTION ARROW
Press the ESC key to exit to the previous menu.
Extinguishant Release Controls
Auto/Manual operation
When in
‘manual’ mode, the following will occur during a detection and release process:
i.
If a zone is enabled and it detects a fire, the panel will log the detection and operate like
normal. All appropriate outputs will activate, sounders will sound, the piezo will activate, etc.
ii.
If a SECOND zone activates, the panel will log the detection but will remain in Fire 1 and will
not advance to Pre-Release or Release.
iii.
If the system is placed back into
‘automatic’ mode, it will then advance to Pre-Release or
Release and proceed like normal.
VIEW CURRENT EVENTS
5. ALL EVENTS
1. FIRE EVENTS
2. FAULT EVENTS
The main
Fire Alarm Controls
may be enabled by
turning the key switch to the controls enabled position
to go from access level 1 to access level 2.
The menus may be navigated by using the
UP / DOWN
keys to move the
required selection to the line with the SELECTION ARROW. Pressing
enter
will then select the chosen option.
The top line shows the current menu name.
In the example below, pressing enter will select the VIEW CURRENT
FIRE EVENTS option.
The extinguishant release switch allows the user to manually
release the extinguishing agent from the RSI. To operate the
switch, the user must pull down the protective cover and then
push the
release
button.
The auto/manual key switch allows the user to place the fire
alarm system in ‘automatic’ or ‘manual’ operation modes. When
set to the default ‘automatic’ mode, the SRP Control Panel will
operate in a normal fashion and will advance to release through
automatic detection methods. The ‘manual’ LED will blink if the
‘manual’
mode has been set from the SRP Control Panel or by
another RSI, and will be continuous if the adjacent key switch has
been turned.
When set to ‘manual’, the SRP Control Panel’s zone circuits will
not advance the system into release. In this mode, the only way
to release the extinguishant is to manually activate it.