 SRP Remote Status Indicator Engineering and Commissioning Manual

 

 

20 
 

Fire Alarm Controls 

 

 

 
The Silence Alarms button will silence any fire alarm sounders that are currently sounding. 
The Reset System button will reset the SRP Control Panel and place the system into a non-alarm state. 
The Sound Alarms button will activate all fire alarm sounders. 
The Silence Buzzer button will silence the buzzer on the SRP Control Panel and all RSI panels. 

System Controls 

 

 

 
 

             SELECTION ARROW 

 

 

Press the ESC key to exit to the previous menu. 

Extinguishant Release Controls 

 

 
 
 
 
 
 
 
 
 
 
 

Auto/Manual operation 

When in 

‘manual’ mode, the following will occur during a detection and release process: 

i. 

If a zone is enabled and it detects a fire, the panel will log the detection and operate like 
normal. All appropriate outputs will activate, sounders will sound, the piezo will activate, etc.  

ii. 

If a SECOND zone activates, the panel will log the detection but will remain in Fire 1 and will 
not advance to Pre-Release or Release. 

iii. 

If the system is placed back into 

‘automatic’ mode, it will then advance to Pre-Release or 

Release and proceed like normal. 

VIEW CURRENT EVENTS

 

   

5. ALL EVENTS 

1. FIRE EVENTS

 

   

2. FAULT EVENTS 

 

The main 

Fire Alarm Controls

 may be enabled by 

turning the key switch to the controls enabled position 
to go from access level 1 to access level 2. 

The menus may be navigated by using the 

UP / DOWN

 keys to move the 

required selection to the line with the SELECTION ARROW. Pressing 

enter

 will then select the chosen option. 

 
The top line shows the current menu name. 
 
In the example below, pressing enter will select the VIEW CURRENT 
FIRE EVENTS option. 

The extinguishant release switch allows the user to manually 
release the extinguishing agent from the RSI.  To operate the 
switch, the user must pull down the protective cover and then 
push the 

release

 button. 

 
The auto/manual key switch allows the user to place the fire 
alarm system in ‘automatic’ or ‘manual’ operation modes.  When 
set to the default ‘automatic’ mode, the SRP Control Panel will 
operate in a normal fashion and will advance to release through 
automatic detection methods. The ‘manual’ LED will blink if the 
‘manual’

 

mode has been set from the SRP Control Panel or by 

another RSI, and will be continuous if the adjacent key switch has 
been turned. 
  
When set to ‘manual’, the SRP Control Panel’s zone circuits will 
not advance the system into release.  In this mode, the only way 
to release the extinguishant is to manually activate it. 

Summary of Contents for TWINFLEX SRP

Page 1: ...62 01 TWINFLEX SRP Fire Suppression System Remote Status Indicator RSI Suitable for TWINFLEX SRP Control Panel from V01 000 Engineering and Commissioning Manual TO BE RETAINED BY THE COMMISSIONING ENG...

Page 2: ...ssioning should only be carried out by competent persons Fike cannot guarantee the operation of any equipment unless all documented instructions are complied with without variation E OE TWINFLEX Mulit...

Page 3: ...ndicator Back Board Power Supply Connections 13 Peripheral Bus Connections 14 SRP Control Panel Connector Board Peripheral Bus Connections 14 Remote Status Indicator Back Board Peripheral Bus Connecti...

Page 4: ...Indicator Specification 25 Fire Alarm System Notice 26 To Enable the Control Panel Keys 26 To Manually Operate the Fire Alarm Sounders 26 Following a Fire Alarm Operation 26 Following a Fault Conditio...

Page 5: ...ntee The equipment carries no warranty unless the system is installed commissioned and serviced in accordance with this manual and the relevant standards by a suitably qualified and competent person o...

Page 6: ...el using the TWINFLEX data protocol Remote Status Indicator RSI The TWINFLEX Remote Status Indicator connects to a Control Panel and reports events that occur on the system It does not connect to any...

Page 7: ...s or in a position that may require access panels to be removed Do not locate the RSI where extremes of temperature or humidity may occur i e close to a heat source or where there is any possibility o...

Page 8: ...TWINFLEX SRP Remote Status Indicator Engineering and Commissioning Manual 8...

Page 9: ...TWINFLEX SRP Remote Status Indicator Engineering and Commissioning Manual 9...

Page 10: ...TWINFLEX SRP Remote Status Indicator Engineering and Commissioning Manual 10 Physical Dimensions...

Page 11: ...TWINFLEX SRP Remote Status Indicator Engineering and Commissioning Manual 11 General Assembly Ribbon Cable Connection Fixing Front Panel To Back Box...

Page 12: ...RSI 2 The cable screen must not be connected to earth ground at any point other than the Control Panel at the SCRN terminal provided Do not connect the screen to a metal back box 3 The cable screen co...

Page 13: ...0V SCRN Screen Screen When powering an RSI from the panel the extra current will reduce the battery backup run time and has to be allowed for in the battery calculations NOTE A jumper wire MUST be ins...

Page 14: ...e second RSI and so on The peripheral bus must not be spurred from one central point SRP Control Panel Connector Board Peripheral Bus Connections There are two sets of peripheral bus connections on th...

Page 15: ...the RELEASE operation The maximum cable length from the EXT SWITCHES connector on the RSI Back Board to the SW1 HOLD and SW2 RELEASE switches is 100 metres The Activation Resistor may be either 680 or...

Page 16: ...orts an RSI Missing fault The RSI must be supervised to be fully functional The Home Screen on the RSI indicates that it is supervised by displaying a check mark next in the upper right corner of the...

Page 17: ...Control Panel The RSI displays the same Home Screen message as the SRP Control Panel lines 2 and 3 If the Home Screen is modified on the SRP Control Panel the Home Screen on the RSI gets updated autom...

Page 18: ...users and responsible persons have been trained properly See the End User Training section below Fault finding If the Date and Time do not update on the RSI and are not in sync with the SRP Control Pa...

Page 19: ...l Panel has reached the release state and release outputs have been activated Continuous The Control Panel has reached the release state and release outputs have been activated and sounders have been...

Page 20: ...T EVENTS 5 ALL EVENTS 1 FIRE EVENTS 2 FAULT EVENTS The main Fire Alarm Controls may be enabled by turning the key switch to the controls enabled position to go from access level 1 to access level 2 Th...

Page 21: ...the Controls Enabled light which shows the level selected as follows RSI Access Level Summary Access Level ACCESS Description Home Screen Display upper right x RSI Address Controls Enabled LED Key Ope...

Page 22: ...ng the enter or ESC button when in Access Level 1 will show the VIEW CURRENT EVENTS Menu with an arrow pointing to the events to be selected for viewing Fire Fault Disable Panel or All events The menu...

Page 23: ...HT The TEST LEDS option causes the panel LEDs to toggle on off and will illuminate to ensure correct operation The test will count down and return to the TEST MODES menu screen The TEST KEYPAD option...

Page 24: ...TUS option displays the current RSI address that is set by the DIL switches A0 to A2 located next to the buzzer The display will time out and return to the STATUS VERSION screen The BUZZER STATUS opti...

Page 25: ...r storage in an accessible and known location in order that the responsible person and the service engineer may keep information records up to date A single page user instruction sheet is included at...

Page 26: ...nel keys turn the key switch off When disabled the Enabled LED should then be extinguished The red FIRE LED will illuminate The fire alarms and the internal buzzer will operate as programmed Take appr...

Page 27: ...___________________________________________________________________________ ADDRESS ______________________________________________________________________ For Service Phone _________________ During Wo...

Page 28: ...rette smoke etc then clear the smoke from the area and press reset on the Control Panel If the alarm state does not re annunciate then no further action is required If the fire alarms in the communal...

Page 29: ...TWINFLEX SRP Remote Status Indicator Engineering and Commissioning Manual 29 Engineers Notes...

Page 30: ...inguishing systems in and around buildings Technical Support Contact your distributor for technical support on this product Do not call the Fike Safety Technology technical support department unless y...

Reviews: