TWINFLEX
®
SRP Control Panel Engineering and Commissioning Manual
18
RSI Peripheral Bus Connections: A1, B1, SCRN or A2, B2, SCRN
These ports on the panel are for connections to a Remote Status Indicator (RSI) device (Maximum 8
devices). This is an RS-485 connection operating at 57.6 kbps.
NOTES
1.
An RSI must be setup to be supervised in order to operate with the SRP. This is done at Access Level
3 (Engineer) at Engineer Menu 13. RSI SUPERVISION.
2.
A 120Ω End of Line (EOL) resistor must be fitted across A and B of the last RSI on the network.