TWINFLEX
®
SRP Control Panel Engineering and Commissioning Manual
57
This allows the selection of subscreens that will allow setting the Type
and Behaviour of the outputs.
This will allow the engineer to view or change the operation of
Monitored Output. Use the
LEFT
and
RIGHT
arrow keys to move the
cursor to a different option and the
UP
and
DOWN
arrow keys to
change the current value. To confirm the changes press
ENTER
.
TYPE:
Notification
– sets the type to a notification device (strobe or sounder)
Release
– sets the output to a releasing type to allow activating a
solenoid device.
This will allow the engineer to view or change the operation of
Monitored Output Use the
LEFT
and
RIGHT
arrow keys to move the
cursor to a different option and the
UP
and
DOWN
arrow keys to
change the current value. To confirm the changes press
ENTER
.
SILENCABLE:
Yes
–
Pressing the silence alarms button will silence the output.
No
–
Pressing the silence alarms button will not silence the output.
STATE:
OFF -
Output is turned off
Alarm
–
Output will activate when the panel in is in the Fire 1(Alarm) state or Sound
Alarms input/button is activated.
Pre-Release
–
Output will activate when panel is in the Fire 2(Pre-Release) state
Release-
Output will activate when panel is in the Release state
PATTERN:
Continuous
–
The output will operate in a continuous (constant) pattern when activated.
Slow
–
The output will operate with a slow (1/2 second on, 1/2 second off) pattern when
activated.
Fast
–
The output will operate with a fast (1/4 second on, 1/4 second off) pattern when
activated.
Temporal
–
The output will operate with a temporal pattern when activated.
User 1-4 -
The output will operate with a user defined pattern when activated. (The user
patterns can only be defined in OSP software)
IMPORTANT NOTE: If the Behaviour of the monitored output is configured and then the Type is changed from
Notification to Releasing or vice versa the panel clears out the Behaviour to default setting.
Default Behaviour is OFF State, Continuous Pattern and Silenceable Output.
11. Panel I/O
2. MONITORED OUTPUTS
11. Panel I/O
1 Type screen
11. Panel I/O
2 Behaviour screen
OUTPUT: 01
STATE: Off
PATTERN: Continuous
SILENCABLE: Yes
OUTPUT OPTIONS
1 Type
2
Behaviour
OUTPUT: 01
TYPE: Notification
NAME: OUTPUT_01
↑/↓ /
→ /← /
Enter
/
Esc