TWINFLEX
®
SRP Control Panel Engineering and Commissioning Manual
58
This will allow the engineer to view or change the operation of
programmable relay 01 - 04. The NAME can be up to 14 characters
long. Use the
LEFT
and
RIGHT
arrow keys to move the cursor to a
different option and the
UP
and
DOWN
arrow keys to change the
current value or option. To confirm the changes press
ENTER
.
STATE:
No State
–
Operation of programmable relay is not configured.
Alarm
–
Operation of programmable relay will be triggered by panel’s Fire 1
Alarm State.
Pre-release
–
Operation of programmable relay will be triggered by panel’s Fire 2 (Pre-
Release) Pre-discharge State.
Release
–
Programmable relay will be triggered by
panel’s Release State.
Extract
–
P
rogrammable relay will be triggered by panel’s Extract State.
Hold
–
P
rogrammable relay will be triggered by panel’s Hold/Abort State.
Disablement
–
P
rogrammable relay will be triggered by panel’s Disable State.
Fault
–
Programmable relay will be triggered by a Fault State.
Manual Mode
–
Programmable relay will be triggered by a Manual Mode State.
Each auxiliary output can be programmed to cycle power during a
system reset, or to keep its power constant during a system reset.
11. Panel I/O
3. Prog Relays
11. Panel I/O
4. AUX Switching
RELAY: 01
STATE: NO STATE
NAME: RELAY 01
↑/↓ /
→ /← /
Enter
/
Esc
AUX POWER SWITCHING
AUX1: Power Constant
AUX2: Power Cycled
↑/↓ /
→ /← /
Enter
/
Esc