26-1369-01
8
Solenoid Connections (J2)
Solenoid connections are power limited and supervised. The Solenoid connection (12 or 24 volt)
requires an EOL circuit supervision assembly (Part# 17-0144), provided by Fike, to be installed between
the SRM and the solenoid coil. The assembly provides a means to monitor the solenoid wiring for open
and short faults.
A single 24V solenoid must be connected as shown in Figure 4. DIL switch SW1 must be in
ON
position
and the solenoid needs to be connected between terminals 1 and 4 at the Solenoid Valve terminal block.
The maximum cable length between the Solenoid and the SRM must not exceed 3 meters.
Figure 4 – 24 Volt Solenoid Connections
Two 12 V solenoids must be connected as shown in Figure 5.
DIL switch SW1 must be in
OFF
position. Solenoid #1 needs to be connected between terminals 1 and 2
and Solenoid #2 needs to be connected between terminals 3 and 4 at the Solenoid Valve terminal block
on the SRM. The maximum cable length between the solenoid and the SRM must not exceed 3 meters.
Figure 5 – 12 Volt Solenoid Connections