Discharge pressure circuit (J4)
The following table shows state of the circuit based on connection type and switch position:
Switch Open
Switch Closed
Normally Open
Normal state
Active state
Normally Closed
Active state
Normal state
Normal state - Circuit is in Normal state.
Active state – The Discharge pressure switch is active which indicates that the extinguishing agent has
been released. The SRP Panel indicates this as a Released condition.
Bottle pressure switch circuit (J5)
The following table shows state of the circuit based on connection type and switch position:
Switch Open
Switch Closed
Normally Open
Normal state
Active state
Normally Closed
Active state
Normal state
Normal state - Circuit is in Normal state.
Active state – Bottle pressure switch is active which indicates that the pressurized container has a leak.
The SRP panel indicates this as a Fault condition.
Solenoid Missing circuit (J6)
The following table shows state of the circuit based on connection type and switch position:
Switch Open
Switch Closed
Normally Open
Normal state
Active state
Normally Closed
Active state
Normal state
Normal state - Circuit is in Normal state.
Active state – It indicates that the solenoid has been physically removed from the releasing agent
container for maintenance or testing. The SRP panel indicates this as a Fault condition.