Quadnet Control Panel Engineering and Commissioning Manual
63
Battery Calculations
Note:
An Excel spreadsheet (document no. 26-1049) is also available to automatically work out both
standby battery calculations and loop loading calculations based on the quantities entered. This
includes ratings for legacy devices as well as the current models listed below.
Current draw ratings for the control panel and current models of devices as at October 2011 are as follows:
PRODUCT DESCRIPTION
QUANTITY
CURRENT DRAWN (mA)
TOTAL (mA)
Product
Code
Description
IS
IA
IS
IA
510 0001
Quadnet Control Panel
1
52.000
111.000
52.000
111.000
Power Supply Unit
10.000
10.000
Loop Card
40.000
40.000
Network Card
22.000
22.000
Output 5 (MO5) (MAX 200mA) depending on external load)
IF USED
N/A
200.000
N/A
Output 6 (MO6) (MAX 200mA) depending on external load)
IF USED
N/A
200.000
N/A
Aux 24VDC (MAX 200mA) depending on external load)
IF USED
200.000
200.000
203 0003
Multipoint Mk3 (from 25/11/09)
0.119
1.985
205 0003
ASD Mk3
0.115
1.996
203 0001
Multipoint with Sounder Mk3 SP0 - OFF
0.119
1.994
Multipoint with Sounder Mk3 SP3 - LOW
0.119
3.013
Multipoint with Sounder Mk3 SP3 - MED
0.119
8.367
Multipoint with Sounder Mk3 SP3 - HIGH
0.119
12.035
205 0001
ASD Mk3 with Sounder SP0 - OFF
0.115
2.071
ASD Mk3 with Sounder SP3 - LOW
0.115
3.090
ASD Mk3 with Sounder SP3 - MED
0.115
8.385
ASD Mk3 with Sounder SP3 - HIGH
0.115
12.167
205 0012
ASD with Sounder/Strobe Mk3 SP0 - OFF
0.115
8.321
ASD with Sounder/Strobe Mk3 SP3 - LOW
0.115
9.340
ASD with Sounder/Strobe Mk3 SP3 - MED
0.115
14.635
ASD with Sounder/Strobe Mk3 SP3 - HIGH
0.115
18.421
403 0006
403 0007
Manual Call Point Mk3
0.173
5.954
313 0001
313 0002
313 0003
Soundpoint Mk3 SP3 - OFF
0.172
2.663
Soundpoint Mk3 SP3 - LOW
0.172
3.615
Soundpoint Mk3 SP3 - MED
0.172
8.046
Soundpoint Mk3 SP3 - HIGH
0.172
11.219
323 0001
Hipoint Mk3 SP3 - OFF
0.176
2.090
Hipoint Mk3 SP3 - LOW
0.176
3.590
Hipoint Mk3 SP3 - MED
0.176
7.988
Hipoint Mk3 SP3 - HIGH
0.176
11.158
303 0013
Bell Mk2 – OFF
0.185
3.192
Bell Mk2 – LOW/MED/HIGH
0.185
46.231
303 0012
303 0022
Flashpoint SP0 - OFF
0.467
2.365
Flashpoint SP3 - LOW
0.467
9.306
Flashpoint SP3 - MED
0.467
13.490
Flashpoint SP3 - HIGH
0.467
16.096
326 0021
326 0023
Sounder/Strobe SP0 - OFF
0.172
18.750
Sounder/Strobe SP3 - LOW
0.172
19.792
Sounder/Strobe SP3 - MED
0.172
23.958
Sounder/Strobe SP3 - HIGH
0.172
28.125
326 0001
326 0003
Sounder SP0 - OFF
0.172
2.740
Sounder SP3 - LOW
0.172
3.615
Sounder SP3 - MED
0.172
8.042
Sounder SP3 - HIGH
0.172
11.183
326 0015
Strobe SP0 - OFF
0.172
18.750
803 0006
Loop I/O Module Mk2
0.461
21.058
803 0010
Conventional Zone Module (Loop Powered)
11.222
48.754
Conventional Zone Module (Ext PSU)
0.402
7.088
803 0005
803 0003
Multipoint I/O Module (Box or Relay Base)
0.030
6.388
600 0092
Remote Indicator
N/A
1.042
N/A
TOTALS
ISTOT (mA)
A
IATOT (mA)
B
TIMES
STANDBY (Hrs)
C
ALARM (Hrs)
D
CURRENT REQUIRED (mAH)
IS
A x C
(mAH)
E
IA
B x D
(mAH)
F
TOTAL CURRENT (mAH)
E
+
F
=
G
TOTAL CURRENT (Ah)
G
/ 1000 =
H
BATTERY REQUIREMENT (Ah)
H
x 1.25 =
J