Quadnet Control Panel Engineering and Commissioning Manual
30
Access Level 2B (Supervisor):
Controls Enabled LED flashing slowly
At Access Level 2B (Supervisor), the main
Fire Alarm Controls
are enabled, and the following
System Controls
are accessible:
1. Delay On/Off
The Delay On/Off function allows pre-configured time delays to be over-ridden or re-instated
manually as required, ie, if sounder operation within a chosen area is programmed to operate after
a time delay, then this delay may be removed or replaced using this function.
2. Test Display
The Test Display function causes the panel LEDs to illuminate, the LCD screen to blacken and the
panel buzzer to sound in order to verify their correct operation.
3. View Logs 1. Current Warnings
The Active Warnings Log will display any current warnings. These are displayed in text format and
may be scrolled through by pressing the
UP
and
DOWN
keys.
1. Delay On / Off
3. Manual Call Point with sounder
5. Sounders & Strobes
4. Manual Call Point
6. Input / Output Modules
7. Conventional Zone Module
6. Network Events
1. All Events
2. By Event Type
3. By Panel
4. By Date
6. Default to all enabled
3. View Logs
2. Multipoint
1. Multipoint with sounder
2. Test Display
1. Current Warnings
3. By Device Type
4. By Loop No - Device No
1. All Events
2. By Event Type
1. User Action
2. Panel Event
3. Fire Event
4. Fault Event
5. By Date
2. Current Faults
3. Current Disablements
4. Current Tests
5. Event Logs
4. Disable / Enable
1. Detection Zone
2. Device
3. Sounders
4. Fire Outputs
5. Fault Outputs
5. Set Time & Date
6. Test Modes
7. Day / Night Mode
1. Silent Test
2. Local Audible Test
1. Override into Day Mode
2. Override into Night Mode
3. End all Overrides
3. System Test
4. View Day / Night settings
8. Find Device