Quadnet Control Panel Engineering and Commissioning Manual
35
1. View Logs 1. Current Warnings
The Active Warnings Log will display any current warnings. These are displayed in text format and
may be scrolled through by pressing the
UP
and
DOWN
keys.
1. View Logs 2. Current Faults
The Active Faults Log will display any current faults. These are displayed in text format and may be
scrolled through by pressing the
UP
and
DOWN
keys.
1. View Logs 3. Current Disablements
The Active Disablement Log will display any current disablements. These are displayed in text
format and may be scrolled through by pressing the
UP
and
DOWN
keys.
1. View Logs 4. Current Tests
The Active Tests Log will display any current test modes. These are displayed in text format and
may be scrolled through by pressing the
UP
and
DOWN
keys.
1. View Logs 5. Event Logs
The Event Log stores 1000 local fire / fault events and 1000 network events which may be
displayed in entirety, or displayed by category. These are displayed in text format and may be
scrolled through by pressing the
UP
and
DOWN
keys.
2. Test Display
The Test Display function causes the panel LEDs to illuminate the LCD screen to blacken and the
panel buzzer to sound in order to verify their correct operation
3. Disable / Enable 1. Detection Zone
This function allows the disablement or enablement of a detection-zone. Thus, all the input devices
(Manual Call Points, detectors and inputs) within that detection-zone will be disabled. The control
panel will indicate that disablements are present, a disablement event will be recorded in the log,
the device LED will still operate when activated and an event will be recorded in the log, but no
programmed actions will occur. The sounder within the device will still operate if triggered from
elsewhere on the system.
3. Disable / Enable 2. Device
This function allows the disablement or enablement of an individual device. The control panel will
indicate that disablements are present, a disablement event will be recorded in the log, the device
LED will still operate when activated and an event will be recorded in the log, but no programmed
actions will occur. The sounder within the device will still operate if triggered from elsewhere on the
system.
3. Disable / Enable 3. Sounders
This function allows the global disablement or enablement of all the sounders on the system. The
control panel will indicate that disablements are present and a disablement event will be recorded
in the log.