Quadnet Control Panel Engineering and Commissioning Manual
32
4. Disable / Enable 5. Fault Outputs
This function allows the global disablement or enablement of all fault outputs on the system. The
control panel will indicate that disablements are present and a disablement event will be recorded
in the log.
4. Disable / Enable 6. Default to All Enabled
This function enables any device / action that may have been disabled, and all programmed actions
are reinstated. The control panel event log will indicate that all actions have been reinstated.
5. Set Time and Date
This allows the time and date to be adjusted.
6. Test Modes 1. Silent Test
The Silent Test function allows the selection of one or more detection-zones to operate in a ‘silent
one-man walk test mode’. On triggering a device the device LED operates and the event is
recorded in the event log as a test activation, but the sounder does not sound and the control panel
does not show an alarm. After approximately 5 seconds the system will reset the device, and
another may be tested. The control panel event log will indicate that a test mode has been
selected.
6. Test Modes 2. Local Audible Test
The Local Audible Test function allows the selection of one or more detection-zones to operate in a
‘one-man walk test mode with local sound’. On triggering a device the device LED operates, the
sounder within that device operates and the event is recorded into the event log as a test activation,
but the control panel does not show an alarm. After approximately 5 seconds the system will reset
the device, and another may be tested. The control panel event log will indicate that a test mode
has been selected.
6. Test Modes 3. System Test
The System Test function allows the entire system to operate in a simple one-man walk test mode.
On triggering a device the device LED operates and the event is recorded in the event log, all the
assigned sounders operate for 10 seconds and the control panel indicates an alarm. After
approximately 10 second the system will reset the device, and another may be tested. The control
panel event log will indicate that a test mode has been selected.
Please note, with the system test mode, only the sounders assigned to operate from that device will
sound, and any delays will still be present. ie. if a delay of 2 minutes is present, the system will
have been reset before the sounders activate.