FIKE CORPORATION
INSTALLATION
U.L. S2203
Expanded Enclosures Installation Guide
Page 17 of 23
F.M. 3009544
Manual P/N: 06-185
Revision No: 1, 11/01
5.0
INSTALLATION
Once the design of the Fire System is complete, the installation can begin.
CAUTION:
Fike Control Systems contain static sensitive components. Handle modules
by the edges only and avoid touching the integrated components. Keep
modules in the protective static bags they were shipped in until time for
installation. Always ground yourself with a proper wrist strap before handling
modules. If the installer is grounded at all times, damage due to static
discharge will not occur. If a module requires repair or return to Fike, it must
be shipped in an anti-static bag.
5.1 INSTALL
BACKBOX/ENCLOSURE
The control panel should be mounted approximately 60” (152.4 cm) from the floor to the middle of the
viewing window on the door. The backbox can be surface or flush mounted as desired. For surface
mounting, utilize the four ‘tear-drop’ openings in the back of the box. For flush mounting, cut the
opening in the wall to fit the backbox, refer to
Section 3.3
for dimensions. Secure the box to the wall
by again utilizing the four ‘tear-drops’ in the back of the enclosure. Reference Section 3 – Equipment
Products for detailed specifications.
Determine the maximum number of conductors needed from the design. Wire is to be brought to the
control panel through backbox via knock-out openings. Conduit knock-outs are provided for two
distinct conduit sizes. 2” conduit can be used by breaking just the inside hole. 2.5” conduit can be
used by removing all of the opening.
Do not install the electronic assemblies into the backbox until the environment is free from
construction dust.
Unless otherwise detailed in this manual or in other documents relating to this control panel, the
designer, installation and service technician, shall utilize published standards and references such as
NFPA 70 National Electrical Code, NFPA 72 National Fire Alarm Code and other standards which
may be relevant to the Local Authority Having Jurisdiction where the control panel will be installed.