10: confIGuratIon
154.
Output 1 - logic of operation
This parameter defines logic of OUT1 output operation.
Parameter size
1B
Default value
0 (NO)
Available
values
0 – contacts normally open / closed when active
1 – contacts normally closed / open when active
155.
Output 2 - logic of operation
This parameter defines logic of OUT2 output operation.
Parameter size
1B
Default value
0 (NO)
Available
values
0 – contacts normally open / closed when active
1 – contacts normally closed / open when active
156.
Output 1 - auto off
This parameter defines time after which OUT1 will be automatical-
ly deactivated.
Parameter size
2B
Default value
0 (auto off disabled)
Available
values
0 – auto off disabled
1-27000 (0.1s-45min, 0.1s step)
157.
Output 2 - auto off
This parameter defines time after which OUT2 will be automatical-
ly deactivated.
Parameter size
2B
Default value
0 (auto off disabled)
Available
values
0 – auto off disabled
1-27000 (0.1s-45min, 0.1s step)
63.
Analog inputs - minimal change to report
This parameter defines minimal change (from the last reported) of
analog input value that results in sending new report. Parameter is
relevant only for analog inputs (parameter 20 or 21 set to 4 or 5).
Parameter size
1B
Default value
5 (0.5V)
Available
values
0 - reporting on change disabled
1-100 (0.1-10V, 0.1V step)