48
Festo — SFAB-...-PNLK — 2022-08
Technical data
SFAB
-10U
-50U
-200U
-600U
-1000U
Electromechanics
Electrical connection
Plug connector, M12x1, A-cod., according to
EN 61076-2-101
Max. connecting cable
length
[m]
30
20 for IO-Link operation
Mechanics
Mounting position
Any
Note on materials for housing
PA-reinforced
Note on materials for inspection
window
PA
Display and operation
Displayable units
–
l/min
–
m
3
/h
–
scfm
–
g/min
–
l
–
m
#
–
scf
–
g
Immission and emission
Storage temperature
[°C]
–20 … +80
Degree of protection in accordance
with EN 60 529
IP65
Standard nominal flow
rate according to
ISO6358/ISO 8778
[l/min]
43.5
163
760
1630
1630
1) Accuracy under nominal conditions (6 bar, 23 °C and horizontal mounting position)
2) % FS =% of the flow rate range end value (full scale)
3) The accuracy of the zero point and accuracy of the spread together correspond to the accuracy of the flow rate: accuracy of the flow
rate = ± (0.3% FS + 3% o.m.v.). % o.m.v. = % of measured value
4) In relation to the flow rate measuring range end value for air
Tab. 29: Technical data
13.1
Examples for calculating the maximum error of the display
–
Flow rate measuring range: 10 … 1000 l/min (FS = 1000)
–
Measured value: 600 l/min