Dismantling
43
11
Fault clearance
Malfunction / display
Possible cause
Remedy
Main display
Lower display
Settings cannot be edited;
‘Lock’ appears.
Security code activated.
–
Enter security code or restore
factory settings
‘Er01’
Error related
Device error.
–
Replace sensor.
‘Er08’
‘ diaP’
Moisture or dirt in the com-
pressed air.
–
Replace sensor.
–200%FS
‘Er09’/‘UNdR’
Below sensing range.
–
Maintain flow measuring
range.
+200%FS
‘Er10’/‘OVER’
Sensing range exceeded
–
Maintain flow measuring
range.
<Measured
value>
‘Er17’/‘SUPL’
Power supply too low.
–
Check power supply.
<Measured
value>
‘Er20’/‘t.Hi’
Temperature error in IO-Link
driver.
–
Eliminate short circuit or
overload.
<Measured
value>
‘Er21’/‘SHRt’
Overload or short circuit at the
OutA, OutC switching output.
–
Eliminate short circuit.
<Measured
value>
‘Er22’/‘SHRt’
Overload or short circuit at the
switching output OutB.
–
Eliminate short circuit.
REC reading
flashes
–
Measured value was outside
the measuring range.
‘Err’ / ‘Id’
‘REPL’
IO-Link DeviceID error, devices
are not identical.
–
When replicating, use sen-
sors with the same meas-
uring range or type.
‘Err’ / ‘COM’
‘REPL’
IO-Link communication error.
–
Check line OutA.
–
Check settings of the device
sensor.
Tab. 28: Fault clearance
12
Dismantling
1. Turn off energy source and compressed air.
2. Disconnect connections from the sensor.
3. For panel mounting: loosen retaining screws.
For H-rail mounting: loosen the mounting slide.