teach values are only accepted after the second teach-in. With the teach-in of the single point mode,
the switching point results from the mean value of the two teaching points: SP = 1/2 (TP1 + TP2). The
keys [A], [B] and [Edit] are locked during the teach-in. The display flashes alternately ‘t-IN’ and ‘IOL’.
1. Set the first desired flow rate.
2. Send the teach-in command 0x4B.
3. Set the second desired flow rate.
4. Send the teach-in command 0x4B.
The teach process is aborted with the command 0x4C.
Recommendation: After teaching, read out the parameter set and check whether the settings match
the application.
8.8
Block parameterisation
Block parameterisation is used to prevent individual parameter values from being incompatible with
the values stored in the device. All parameters transmitted as a block will be simultaneously accepted
and activated.
Index
Subindex
Name
0x003C
(60)
0x01
Setpoint SP1
0x02
Setpoint SP2
0x003D
(61)
0x02
Switchpoint mode
0x03
Hysteresis
Tab. 19: Block parameterisation for flow rate monitoring SSC1.1 (OutA)
Index
Subindex
Name
0x003E
(62)
0x01
Setpoint SP1
0x02
Setpoint SP2
0x003F
(63)
0x02
Switchpoint mode
0x03
Hysteresis
Tab. 20: Block parameterisation for flow rate monitoring SSC1.2 (OutB)
Index
Subindex
Name
0x3142
(12610)
0x00
Threshold of volume / mass pulse
0x0149
(329)
0x00
Volume /mass pulse length
Tab. 21: Block parameterisation for volume pulse/mass pulse SSC1.3 (OutC)
Index
Subindex
Name
0x400C
(16396)
0x01
Setpoint SP1
0x02
Setpoint SP2