Festo — SFAB-...-PNLK — 2022-08
Product overview
systems via switching outputs, a volume switching pulse, an analogue output or an IO-Link interface.
Depending on the configuration, the switching outputs monitor a threshold value or a signal range.
The outputs can be set as PNP or NPN and normally open (NO) or normally closed (NC). The analogue
output can be operated either as a voltage output or as a current output. Through the IO-Link
interface, process values can be read out and parameters changed and transmitted to additional
devices. If the flow rate is integrated, a volume signal or mass signal can be calculated and output via
a pulse output and an accumulated measured value via IO-Link.
flow rate q
temperature t
FLOW
flow rate q
VOL or MASS
volume or mass pulse VMP
REC
volume or mass recorder VMR
tEMP
temperature t
FLOW (OutA)
FLOW (OutB)
PULS (OutC)
binary q / SSC1.1
binary q / SSC1.2
binary VMP / SSC1.3
FLOW
analogue q / MDC1
analogue t / MDC2
tEMP
Pin 4
q or VMP
q or t
Pin 2
Fig. 3: Signal structure SFAB
4.2.2
Operating statuses
Operating status
Function
RUN mode
–
Basic state after the operating voltage has been applied.
–
Display of the current measured value.
–
Display of the selected inputs and outputs.
–
Switchover between the measured variables of flow rate, volume and
temperature.
SHOW mode
–
Display of the current settings for the switching outputs and the ana-
logue output.
–
Display and reset of the minimum and maximum values.
–
Display of the average flow rate measurement.
EDIT mode
–
Setting or modification of parameters.
TEACH mode
–
Acceptance of the current measured value to specify switching points.
RECORDER mode
–
Manual measurement of the accumulated volume.
Tab. 3: Operating statuses SFAB