SDE3−...
Festo SDE3−... 0604a English
50
11
Trouble−shooting
Fault
Possible cause
Remedy
No display
Supply voltage not applied
or no permitted operating
voltage
Switch on supply voltage /
maintain permitted
operating voltage range
Electrical connections
swapped (incorrect polarity)
Wire the SDE3−... as shown
in the circuit diagram.
SDE3−... defective
Return SDE3−... to Festo
Error number Er17
flashes (see also Fig.19)
Undervoltage in the power
supply
Observe permitted
operating voltage range
Error number Er01
flashes
SDE3−... defective
Return SDE3−... to Festo
Incomplete display
Display defective
Return SDE3−... to Festo
Incorrect pressure
display
Pneumatic connections
swapped (only with SDE3−..D
or SDE3−..Z)
Connect tubing in
accordance with section
Pneumatic installation"
SDE3−... operated with
non−permitted medium
Replace the SDE3−... and
operate only with
compressed air
Pressure display flashes
or error number Er09 ...
Er12 flashes
Pressure outside measuring
range
Observe permitted pressure
measuring range
Er12 flashes
(see also Fig.19)
Excess pressure over
maximum permitted value
(device damaged)
Replace SDE3−...
Outputs do not switch
according to settings.
Short circuit/overload at
relevant output
Eliminate short
circuit/overload
SDE3−... defective
Return SDE3−... to Festo
Settings cannot be
edited (Lock" in the
display)
Access protection active
Enter security code
(if security code is lost, reset
the SDE3−... to the factory
setting, see section 7)
Fig.18
Summary of Contents for SDE3 series
Page 27: ...SDE3 Festo SDE3 0604a Deutsch 27 Bild 23 EDIT Modus ...
Page 28: ...SDE3 Festo SDE3 0604a Deutsch 28 Bild 24 TEACH Modus ...
Page 30: ...SDE3 Festo SDE3 0604a Deutsch 30 ...
Page 55: ...SDE3 Festo SDE3 0604a English 55 Fig 23 EDIT mode ...
Page 56: ...SDE3 Festo SDE3 0604a English 56 Fig 24 TEACH mode ...