BLUEHELIX TECH RRT 24 H
191
EN
cod. 3541C661 - Rev. 00 - 10/2018
Table of faults
Table. 9- List of faults
Fault code
Fault
Possible cause
Cure
A01
No burner ignition
No gas
Check the regular gas flow to the boiler and
that the air has been eliminated from the pipes
Ignition/detection electrode fault
Check the wiring of the electrode and that it is
correctly positioned and free of any deposits;
replace the electrode if necessary.
Faulty gas valve
Check the gas valve and replace it if neces-
sary
Insufficient gas supply pressure
Check the gas supply pressure
Trap blocked
Check the trap and clean it if necessary
Air/fume ducts obstructed
Remove the obstruction from the flue, fume
extraction ducts, air inlet and terminals.
A02
Flame present signal with burner off
Electrode fault
Check the ionization electrode wiring
Check the condition of the electrode
Electrode to earth
Cable to earth
Check the trap and clean it if necessary
Card fault
Check the card
A05
Fan fault
No 230V power supply
Check the 5-pin connector wiring
Tachometric signal interrupted
Fan damaged
Check the fan
A06
No flame after the ignition phase
Ionization electrode fault
Check the position of the ionization electrode
and replace it if necessary
Flame unstable
Check the burner
air/fume ducts obstructed
Remove the obstruction from the flue, fume
extraction ducts, air inlet and terminals
Trap blocked
Check the trap and clean it if necessary
F07 - F14 - A07
High fume temperature
The fume probe detects an exces-
sive temperature
Check the exchanger
Check the flue gas probe
F08
A08
Overtemperature protection inter-
vention
Heating sensor damaged
Check the correct positioning and operation of
the heating sensor and replace it if necessary
No water circulation in the system
Check the circulating pump
Air in the system
Vent the system
F09
A09
Overtemperature protection inter-
vention
Return sensor damaged
Check the correct positioning and operation of
the return sensor and replace it if necessary
No water circulation in the system
Check the circulating pump
Air in the system
Vent the system
F10
A10
Delivery sensor fault
Sensor damaged
Check the wiring or replace the sensor
Wiring shorted
Wiring disconnected
F11
A11
Return sensor fault
Sensor damaged
Check the wiring or replace the sensor
Wiring shorted
Wiring disconnected
F12
DHW sensor fault
Sensor damaged
Check the wiring or replace the sensor
Wiring shorted
Wiring disconnected
F13
A13
Fume probe fault
Probe damaged
Check the wiring or replace the fume probe
Wiring shorted
Wiring disconnected
A14
Fume extraction duct safety device
intervention
Fault F07 generated 3 times in the
last 24 hours
See fault F07
F34
Supply voltage under 170V
Electric mains trouble
Check the electrical system