"Sc" - Combustion Control Parameters Menu
ONLY QUALIFIED PERSONNEL CAN ACCESS THE "SC" MENU AND MODIFY THE RELEVANT PARAMETERS.
Press the Heating buttons to scroll the list of parameters in increasing or decreasing order. Press the DHW buttons to
view or modify the value of a parameter. To save the edited parameter press either the
h”
or
“-”
button (details
3 and 4 - fig. 1).
PARAMETERS "SC12" AND "SC13" MUST BE MODIFIED, IF STRICTLY NECESSARY, BY QUALIFIED PERSON-
NEL AND ONLY WHEN THE CO
2
VALUES ARE OUTSIDE THE RANGE INDICATED IN “- Technical data table”
on page 196. CARRY OUT THE PROCEDURE AFTER AT LEAST 500 HOURS OF BOILER OPERATION.
* SC12
regulates the CO
2
at the same time at maximum and minimum power. By increasing the parameter value the
CO
2
decreases; by decreasing the parameter value the CO
2
increases.
** SC13
regulates the CO
2
at minimum power. By increasing the parameter value the CO
2
decreases; by decreasing
the parameter value the CO
2
increases.
Contents Description
Functional description
Range
Default
Sc01
Gas type selection
Allows the change of gas type. See “Gas conversion” on
page 170
na / LP
na
Sc02
Ignition gas calibration
Allows the amount of gas to be increased or decreased in
the ignition phase in case of difficult starting.
-9 ÷ 20
0
Sc03
Ignition power
Allows the fan speed to be increased or decreased in the
ignition phase in case of difficult starting.
-16 ÷ 14
0
Sc04
Flue length
Allows the boiler to be arranged according to the width
and length of the flue used. To be used only with Ø50 or
Ø60 flues. See fig. 27.
-2 ÷ 13
0
Sc05
Minimum power calibration
Allows the minimum power to be increased, if necessary. 0 ÷ 25
0
Sc06
Minimum gas valve calibration
Self-adaptive parameter.
DO NOT MODIFY
.
Sc07
Flame ionization signal
Displays the actual ionization current signal.
Read only
Sc08
Current power ref. DHW
Displays the actual power referred to maximum power in
DHW.
Read only
Sc09
MAX ionization value
Displays the maximum ionization value reached.
Read only
Sc10
Minimum ionization value during ignition
Displays the minimum ionsation value reached during the
ignition phase.
Read only
Sc11
Ignition time
Displays the time from fan activation to ionization.
Read only
Sc12
*
Ionization reduction value (BASE)
Allows the adjustment of CO
2
at the same time as maxi-
mum and minimum power, translating the entire value
curve.
-5 ÷ 10
0
Sc13
**
Ionization reduction value (min.)
Allows the adjustment of CO
2
at minimum power.
-5 ÷ 10
0
Sc14
Internal error K1
Displays the SCOT system error code.
Read only
Sc15
100% CALIBRATION
Allows 100% Calibration (see “100% calibration” on
page 172) when replacing some components (see
“Extraordinary maintenance and replacement of compo-
nents” on page 183)
0 - CAL
0
Sc16
DO NOT MODIFY
.