BLUEHELIX TECH RRT 24 H
177
EN
cod. 3541C661 - Rev. 00 - 10/2018
Notes:
1. Parameters with more than one description vary their function and/or range in relation to the setting of the parameter
given in brackets.
2. Parameters with more than one description are reset to the default value if the parameter given in brackets is modified.
3. The Maximum Heating Power parameter can also be modified in Test Mode.
Press the Reset button to return to the Service Menu. Press the Reset button for 20 seconds to exit the card Service
Menu, or exiting occurs automatically after 15 minutes.
P51
Solar deactivation temperature (b01=1)
0-100°C
10°C
Setpoint deltaT (b01=2)
0-20°C
0°C
Solar deactivation temperature (b01=3)
0-100°C
10°C
Setpoint deltaT (b01=4)
0-20°C
0°C
P52
Solar ignition temperature (b01=1)
0-100°C
10°C
DHW ramp (b01=2)
1-20°C/minute
5°C/minute
Solar ignition temperature (b01=3)
0-100°C
10°C
DHW ramp (b01=4)
1-20°C/minute
5°C/minute
P53
Solar standby time (b01=1)
0-255 seconds
10 seconds
No effect on adjustment (b01=2)
0-255 seconds
0 seconds
Solar standby time (b01=3)
0-255 seconds
10 seconds
No effect on adjustment (b01=4)
0-255 seconds
0 seconds
P54
Heating deltaT temperature adjustment (b01=1)
0-60°C
18°C
Heating deltaT temperature adjustment (b01=2)
0-60°C
18°C
Heating deltaT temperature adjustment (b01=3)
0-60°C
18°C
Heating deltaT temperature adjustment (b01=4)
0-60°C
18°C
P55
Primary exchanger protection temperature (b01=1)
0-150°C
43°C
Primary exchanger protection temperature (b01=2)
0-150°C
43°C
Primary exchanger protection temperature (b01=3)
0-150°C
43°C
Primary exchanger protection temperature (b01=4)
0-150°C
43°C
P56
System min. pressure value
0-8bar/10 (Only for boilers with water pressure
sensor)
4 bar/10
P57
System nominal pressure value
5-20bar/10 (Only for boilers with water pressure
sensor)
7 bar/10
P58
Exchanger protection intervention (b01=1)
0=No F43, 1-15=1-15°C/second
10°C/second
Exchanger protection intervention (b01=2)
0=No F43, 1-15=1-15°C/second
10°C/second
Exchanger protection intervention (b01=3)
0=No F43, 1-15=1-15°C/second
10°C/second
Exchanger protection intervention (b01=4)
0=No F43, 1-15=1-15°C/second
10°C/second
P59
Heating hysteresis after ignition
6-30°C
10°C
P60
Timer for heating hysteresis after ignition
60-180seconds
60seconds
Contents Description
Range
Default