BLUEHELIX TECH RRT 24 H
159
EN
cod. 3541C661 - Rev. 00 - 10/2018
2. Installation
2.1 General Instructions
BOILER INSTALLATION MUST ONLY BE PERFORMED BY QUALIFIED PERSONNEL, IN ACCORDANCE WITH
ALL THE INSTRUCTIONS GIVEN IN THIS TECHNICAL MANUAL, THE PROVISIONS OF CURRENT LAW, THE PRE-
SCRIPTIONS OF NATIONAL AND LOCAL STANDARDS AND THE RULES OF PROPER WORKMANSHIP.
2.2 Place of installation
B
The combustion circuit is sealed with respect to the place of installation and therefore the unit can be
installed in any room except in a garage. The place of installation must be sufficiently ventilated to pre-
vent the creation of dangerous conditions in case of even small gas leaks. Otherwise there may be a
risk of suffocation and intoxication or explosion and fire. This safety precaution is required by EEC
Directive No. 2009/142 for all gas units, including so-called sealed chamber units.
The unit is designed to operate in a partially protected place, with a minimum temperature of -5°C. If provided with the
special antifreeze kit, it can be used with a minimum temperature down to -15°C. The boiler must be installed in a shel-
tered place, for instance under the slope of a roof, inside a balcony or in a protected recess.
The place of installation must be free of flammable materials, objects and dusts or corrosive gases.
The boiler is arranged for wall mounting and comes as standard with a hooking bracket. Wall fixing must ensure stable
and effective support for the generator.
A
If the unit is enclosed in a cabinet or mounted alongside, there must be sufficient space for removing the casing
and for normal maintenance activities
2.3 Plumbing connections
Important
B
The safety valve outlet must be connected to a funnel or collection pipe to prevent water spurting onto the floor
in case of overpressure in the heating circuit. Otherwise, if the discharge valve cuts in and floods the room,
the boiler manufacturer cannot be held liable.
B
Before installation, flush all the pipes of the system thoroughly to remove any residuals or impurities that could
affect proper operation of the unit.
In case of replacement of generators in existing installations, the system must be completely emptied and
cleaned of any sludge and pollutants. For that purpose only use suitable guaranteed products for heating sys-
tems (see next section), that do not harm metals, plastics or rubber.
The manufacturer declines any liability
for damage caused to the generator by failure to properly clean the system
.
Make the connections to the respective points (see fig. 51, fig. 52 and fig. 53) and to the symbols given on the unit.
Plumbing kit (optional)
A kit of fittings (code 012044W0) for the hydraulic con-
nection of the boiler to the wall is available on request.
7 -
Gas inlet
9 -
Tap water inlet
10 -
System delivery
11 -
System return
fig. 18- Plumbing kit
10
7
11
9