BLUEHELIX MAXIMA
216
EN
cod. 3541U630 - Rev. 03 - 11/2020
2. Parameters with more than one description are reset to the default value if the parameter given
in brackets is modified.
3. The Maximum Heating Power parameter can also be modified in Test Mode.
To return to the service menu, simply touch the "arrow" icon
in the top left corner of the screen.
Combustion Control Menu
ONLY QUALIFIED PERSONNEL CAN ACCESS THE MENU AND MODIFY THE RELEVANT
PARAMETERS.
ZTP (Sliding temperature) Parameters Menu
When the external probe is installed, the boiler adjustment system works with "Sliding Tempera-
ture". In this mode, the heating system temperature is regulated according to weather conditions,
to ensure high comfort and energy efficiency throughout the year. In particular, as the outside tem-
perature increases the system flow temperature decreases according to a specific "compensation
curve".
With Sliding Temperature adjustment, the temperature set using the buttons [+] (detail 12 fig.1)
and [-] (detail 14 fig.1) becomes the maximum system flow temperature. It is advisable to set a
maximum value to allow system adjustment throughout its useful operating range.
The boiler must be adjusted at the time of installation by qualified personnel. However, the user
can make any further adjustments necessary to optimize comfort levels.
Compensation curve and curve offset
The settings of the compensation curves and relevant offset can be accessed via the service
menu and touching the item [ZTP parameters]. Use fig. 25 as a reference for choosing the value
of curve-type parameters and fig. 26 as a reference for choosing the value of offset-type parame-
ters.
If the room temperature is lower than the required value, it is advisable to set a higher order curve
and vice versa. Proceed by increasing or decreasing in steps of one and check the result in the
room.
Code
Description
Functional description
Range
Default
Sc01
Gas type selection
Allows the change of gas type. See “Gas conver-
sion” on page 210
NG/LPG
NG
Sc02
Ignition gas calibration
Allows the amount of gas to be increased or decrea-
sed in the ignition phase in case of difficult starting.
-9 ÷ 20
0
Sc03
Ignition power
Allows the fan speed to be increased or decreased
in the ignition phase in case of difficult starting.
-16 ÷ 14
0
Sc04
Flue length
Allows the boiler to be arranged according to the
width and length of the flue used. To be used only
with Ø50 or Ø60 flues. See fig. 19.
-2 ÷ 13
0
Sc05
Minimum power calibration
Allows the minimum power to be increased, if
necessary.
0 ÷ 25
0
Sc06
Minimum gas valve calibration
Self-adaptive parameter.
DO NOT MODIFY
.
Sc07
Flame ionization signal
Displays the actual ionization current signal.
Read only
Sc08
Current power ref. DHW
Displays the actual power referred to maximum
power in DHW.
Read only
Sc09
MAX ionization value
Displays the maximum ionization value reached.
Read only
Sc10
Minimum ionization value during ignition
Displays the minimum ionization value reached
during the ignition phase.
Read only
Sc11
Ignition time
Displays the time from fan activation to ionization.
Read only
Sc12
*
Ionization reduction value (BASE)
NOT MODIFIABLE
Read only
0
Sc13
**
Ionization reduction value (min.)
NOT MODIFIABLE
Read only
0
Sc14
Internal error K1
Displays the SCOT system error code.
Read only
Sc15
100% CALIBRATION
Allows 100% Calibration (see “100% calibration” on
page 211) in case of replacement of several compo-
nents
0 - 1
0