background image

} }

T

E

S

R1 

FIRST DETECTOR BASE 

LAST DETECTOR BASE 

AUX. RELAY 

AUX. RELA

AUX.

Y

RELAY

RA-914 

CONTACTS 

RA-914 

CONT

RA-914

ACTS

CONTACTS

REMOTE LED/ 

FORM C 

REMOTE LED/ 

FORM C

REMOTE LED/

FORM C

TEST SWITCH 

TEST SWITCH

TEST SWITCH

RED 

RED

RED

4

5

4

5

4

END OF 
LINE 

6

BROWN 

24 VDC 

-

6

6

3

3

BROWN

BROWN

PINK 

(4WRM) 

FACTORY WIRED, 
DO NOT REMOVE 

7

88

RELAY 

END OF 

PINK

PINK

(4WRM) 

3

3

LINE 
DEVICE 

FACTORY WIRED, 
DO NOT REMOVE 

TO CONTROL 
PANEL 
INITIATING 
CIRCUIT 

Figure 5. Detector Using 4-Wire 4WRB Base with Relay Module

BASE OPTIONS

LOCKING FEATURE
The detector bases include a locking feature that prevents removal of the detector without using a tool. To eliminate this feature, break off the locking

tab shown in Figure 6, then install the detector. To remove the detector from the base once the locking feature has been activated, insert a small
screwdriver into the slot on the base to push the plastic tab while simultaneously turning the detector head counterclockwise (see Figure 6).

Use small bladed screwdriver 

to push locking tab

Test 
magnet 

position 

BREAK PLASTIC TAB 
BY TWISTING TOWARD 
CENTER OF BASE 

1.  BODY 
2.  CONTACT ARM 

2

3.  CONTACT SPRING 
4.  TERMINAL PLATE 

5.  JUMPER WIRE (remove before 

installation of detector head) 

6.  TERMINAL SCREW 
7.  R1: RESISTOR (with cover) 

Figure 6. Detector Using 2-Wire Base (Less Options)

RELAY MODULES
Relay Modules are not recommended for stand-alone operation. The installation and allowable configurations of the 2-wire 2WRM and 4 wire 4WRM

are as follows:

Model 2WRM

Install a 2WRM into a 2WRLT base to function as a 2WRB as follows:

1.

Remove resistors connected to terminals 2 to 3 and 3 to 4 on the 2WRLT base.

2.Insert the 2WRM into the base.

3.Secure into position by twisting clockwise as shown in Figure 7.

4.Wire the 2WRM and base according to Figure 4.

5.Secure the wire under terminals 3 and 4 shown in Figure 7

.

 

www.fenwal-direct.eu

www.prevent-a-fire.eu 

 

Model: 4WRB 

 

 

Sensor bottom view: 

 

Summary of Contents for PSD Series

Page 1: ...www fenwal direct eu www prevent a fire eu Smoke Detector PSD 2 4 Wire Units ...

Page 2: ...re detection feature rated at 15 F 8 3 C per minute All detectors are designed for 2 Wire and 4 Wire installation using the appropriate Detector bases The Smoke and Heat Detectors are UL Listed fo Open Area Protection applications per UL 268 and UL 521 respectively Detectors may also be installed in systems intended for Releasing Devic Service through use of a compatible Fire Alarm Control Panel D...

Page 3: ...iling obstructions high air exchange rates etc reduced spacing must be used to achieve adequat protection Computer rooms and other such installations may require spacing with a maximum of 200 square feet 18 6 m2 due to high air exchang rates For additional information consult NFPA 72 and the Fenwal Automatic Fire Detection Application Engineering Manual MC 402 Per UL Listing open area smoke detect...

Page 4: ...m is required 6 Locate detectors on the downstream side of filters to sense fires in the filters However it should be noted that should the filters block the ai flow sufficient air flow may no longer be present for proper operation of the duct detector 7 Locate detectors whenever possible where they can be conveniently observed and readily serviced 8 Locate detectors in return air ducts ahead of m...

Page 5: ...EST SWITCH 3 6 5 4 RA 914 REMOTE LED TEST SWITCH 3 6 5 4 END OF PANEL LINE DEVICE CIRCUIT Figure 3 Detector Using 2 Wire 2WRLT Base with Remote Indicator and Remote Test Switch Optio FIRST DETECTOR BASE LAST DETECTOR BASE AUX RELAY AUX AUX RELA RELAY Y RA 914 CONTACTS RA 914 RA 914 CONT CONTACTS ACTS REMOTE LED FORM C REMOTE REMOTE LED LED FORM FORM C C TO CONTROL PANEL INITIATING CIRCUIT 8 7 3 6 ...

Page 6: ... been activated insert a smal screwdriver into the slot on the base to push the plastic tab while simultaneously turning the detector head counterclockwise see Figure 6 Use small bladed screwdriver 1 to push locking tab Test magnet 4 position 7 5 BREAK PLASTIC TAB BY TWISTING TOWARD CENTER OF BASE 1 BODY 2 CONTACT ARM 3 2 6 3 CONTACT SPRING 4 TERMINAL PLATE 5 JUMPER WIRE remove before installation...

Page 7: ...ING FENWAL SERIES 70 201000 XXX BASE RETROFIT ADAPTER MA 001 P N 70 501000 003 CPD 705x PSD 715x THD 705x Figure 8 Installing Mechanical Adapter MA 00 DETECTOR TESTING AND SENSITIVITY METERIN FREQUENC Testing shall be performed upon installation of the detector and once a year thereafter as stated in NFPA 72 latest edition Smoke Detector sensitivit shall be metered within one year of installation ...

Page 8: ... should alarm as indicated by stead illumination of the alarm indicator LEDs To return each detector to normal operation reset the control unit 4 Failure to alarm in test 3 indicates a defective detector requiring service 5 After taking appropriate corrective action re engage Alarm Signal Devices Releasing Devices and Extinguishing Systems and ensure that th entire system is returned back to norma...

Page 9: ...y Module 70 500000 102 4WRM Spare 4 Wire Relay Module DETECTOR ACCESSORIE Part No Model Description 06 117883 001 Test Magnet 29 116788 001 EOL Supervisory Relay 70 200000 911 RA 911 Remote Alarm Indicator 70 200000 914 RA 914 Remote Alarm Indicator w Smoke Detector Test Switch 70 500000 002 ST 001 Smoke Detector Sensitivity Tester 70 500000 003 DST 003 Wireless Infrared Smoke Detector Sensitivity...

Reviews: