SIGA2-PHS(B) Intelligent 3D Multisensor Photo-
Heat Detector Installation Sheet
Description
The Signature Series Intelligent 3D Multisensor Photo-Heat
Detector is an intelligent device that contains a photoelectric
smoke sensor and a fixed-temperature heat sensor. There are
two models: SIGA2-PHS is white; SIGA2-PHSB is black.
LED indicator.
The LED indicator (see Figure 1 below)
displays the following states:
•
Normal: Green LED indicator flashes, no action.
•
Alarm/active: Red LED indicator flashes, evacuate the
area.
•
Stand-alone alarm: Red LED indicator turns on, evacuate
the area.
Figure 1: SIGA2-PHS(B) features
3
1
2
1.
Tamper-resist lever arm on base
2.
Access slot for tamper-resist mechanism
3. LED
indicator
Installation
Notes
•
This detector does not operate without electrical power. As
fires frequently cause power interruption, discuss further
safeguards with the local fire protection specialist.
•
This detector does not sense fires in areas where smoke
or heat cannot reach the detector. Smoke or heat from
fires in walls, roofs, or on the opposite side of closed doors
may not reach the detector.
•
Photoelectric detectors have a wide range of sensing
capabilities, and are best suited for detecting slow,
smoldering fires. The heat sensor in this device provides a
source of supplemental information. The heat sensor by
itself does not provide life safety protection.
•
To ensure proper operation, store the detector within the
recommended ranges. Allow the detector to stabilize to
room temperature before applying power.
•
The dust cover (supplied) must remain on the detector
during installation and be removed prior to commissioning
and service. The dust cover is not a substitute for
removing the detector during new construction or heavy
remodeling.
•
In Canada, install according to the CAN/ULC-S524
Standard for the Installation of Fire Alarm Systems,
the
CSA
C22.1
Canadian Electrical Code
, and the local
authority having jurisdiction.
•
Upon completion of the original installation and following
any modifications or additions to the system, perform a
calibrated sensitivity test per NFPA code. Signature Series
devices can perform this test and the panel can generate
a system sensitivity report.
•
To permanently disable the tamper-resist mechanism prior
to placing the detector in difficult to reach locations, break
and remove the plastic lever arm from the base. See
Figure 1, item 1.
To install the detector:
1. Install and wire the base, as described on the installation
sheet supplied with the base.
2. Remove the serial number label from the detector and
attach it to the project documentation.
3. Attach the detector to the base by rotating the detector
clockwise until it snaps into the locked position.