SIGA2-PHS(B) Intelligent 3D Multisensor Photo-

Heat Detector Installation Sheet 

 

 

Description  

The Signature Series Intelligent 3D Multisensor Photo-Heat 
Detector is an intelligent device that contains a photoelectric 
smoke sensor and a fixed-temperature heat sensor. There are 
two models: SIGA2-PHS is white; SIGA2-PHSB is black. 

LED indicator. 

The LED indicator (see Figure 1 below) 

displays the following states: 

• 

Normal: Green LED indicator flashes, no action. 

• 

Alarm/active: Red LED indicator flashes, evacuate the 
area. 

• 

Stand-alone alarm: Red LED indicator turns on, evacuate 
the area. 

Figure 1: SIGA2-PHS(B) features 

3

1

2

 

1. 

Tamper-resist lever arm on base 

2. 

Access slot for tamper-resist mechanism 

3. LED 

indicator 

Installation  

Notes

 

• 

This detector does not operate without electrical power. As 
fires frequently cause power interruption, discuss further 
safeguards with the local fire protection specialist. 

• 

This detector does not sense fires in areas where smoke 
or heat cannot reach the detector. Smoke or heat from 
fires in walls, roofs, or on the opposite side of closed doors 
may not reach the detector. 

• 

Photoelectric detectors have a wide range of sensing 
capabilities, and are best suited for detecting slow, 
smoldering fires. The heat sensor in this device provides a 
source of supplemental information. The heat sensor by 
itself does not provide life safety protection. 

• 

To ensure proper operation, store the detector within the 
recommended ranges. Allow the detector to stabilize to 
room temperature before applying power. 

• 

The dust cover (supplied) must remain on the detector 
during installation and be removed prior to commissioning 
and service. The dust cover is not a substitute for 
removing the detector during new construction or heavy 
remodeling. 

• 

In Canada, install according to the CAN/ULC-S524 

Standard for the Installation of Fire Alarm Systems,

 the 

CSA

 

C22.1 

Canadian Electrical Code

, and the local 

authority having jurisdiction. 

• 

Upon completion of the original installation and following 
any modifications or additions to the system, perform a 
calibrated sensitivity test per NFPA code. Signature Series 
devices can perform this test and the panel can generate 
a system sensitivity report. 

• 

To permanently disable the tamper-resist mechanism prior 
to placing the detector in difficult to reach locations, break 
and remove the plastic lever arm from the base. See 
Figure 1, item 1. 

To install the detector: 

1.  Install and wire the base, as described on the installation 

sheet supplied with the base. 

2.  Remove the serial number label from the detector and 

attach it to the project documentation. 

3.  Attach the detector to the base by rotating the detector 

clockwise until it snaps into the locked position. 

© 2011 UTC Fire & Security. All rights reserved. 

1 / 4 

P/N 3101548 • REV 2.0 • ISS 10AUG11 