Fenwal PSD Series Installation Instructions Manual Download Page 7

Model 4WRM

Install a 4WRM into a 2WRLT or 2WRB base to function as a 4WRB as follows:

1.Remove resistors connected to terminals 2 to 3 and 3 to 4 if converting the 2WRLT base.

 Remove the 2WRM if converting the 2WRB.

2.Insert the 4WRM into the base.

3.Secure into position by twisting clockwise as shown in Figure 7.

4.Wire the 4WRM and base according to Figure 5.
5.Secure the wire under terminals 3 and 4 shown in Figure 7.

4

RELAY MODULE 
2WRM OR 4WRM 

70-50100-XXX BASE 

Figure 7. Relay Module

MECHANICAL RETROFIT ADAPTER (MA 001)
The MA-001 (P/N 70-501000-003) is used to allow all old style Fenwal bases (Series 70 201000-XXX) to accept the CPD-705X, PSD-715X and THD-
705X detectors. No rewiring is required to retrofit the base. Install as follows:

1.Align the components as shown in Figure 8.

2.Mate the MA-001 to the existing base and twist clockwise to lock in.
3.Mate the new detector to the MA-001 and twist clockwise to secure.

EXISTING FENWAL 
SERIES 70-201000-XXX 
BASE 

RETROFIT 
ADAPTER MA-001 
P/N 70-501000-003 

CPD-705x 
PSD-715x 
THD-705x 

Figure 8. Installing Mechanical Adapter MA-001

DETECTOR TESTING AND SENSITIVITY METERING

FREQUENCY
Testing shall be performed upon installation of the detector and once a year thereafter as stated in NFPA-72 latest edition. Smoke Detector sensitivity

shall be metered within one year of installation and every alternative year thereafter as stated in NFPA 72. 

The Authority having jurisdiction may

dictate which test to perform.

GO-NO GO TEST FOR SMOKE (CPD & PSD) DETECTORS

Equipment Required

•

Test Magnet P/N 06-117883-001, OR

•

Canned Smoke

Test Method

1.

Disengage Alarm Signal Devices, Releasing Devices and Extinguishing Systems prior to performing the following test.

2.Use extreme caution when using magnet in EDP Facilities.

 To be safe, notify EDP management of the intent to use a magnet in their facilities.

3.After powering the detector head for approximately 1 minute, check to see that the indicator LEDs flash.

 Failure to flash indicates a

nonfunctioning detector or faulty wiring. Recheck wiring and replace detector head if necessary.

 

Model: 4WRB 

 

Summary of Contents for PSD Series

Page 1: ...www fenwal direct eu www prevent a fire eu Smoke Detector PSD 2 4 Wire Units ...

Page 2: ...re detection feature rated at 15 F 8 3 C per minute All detectors are designed for 2 Wire and 4 Wire installation using the appropriate Detector bases The Smoke and Heat Detectors are UL Listed fo Open Area Protection applications per UL 268 and UL 521 respectively Detectors may also be installed in systems intended for Releasing Devic Service through use of a compatible Fire Alarm Control Panel D...

Page 3: ...iling obstructions high air exchange rates etc reduced spacing must be used to achieve adequat protection Computer rooms and other such installations may require spacing with a maximum of 200 square feet 18 6 m2 due to high air exchang rates For additional information consult NFPA 72 and the Fenwal Automatic Fire Detection Application Engineering Manual MC 402 Per UL Listing open area smoke detect...

Page 4: ...m is required 6 Locate detectors on the downstream side of filters to sense fires in the filters However it should be noted that should the filters block the ai flow sufficient air flow may no longer be present for proper operation of the duct detector 7 Locate detectors whenever possible where they can be conveniently observed and readily serviced 8 Locate detectors in return air ducts ahead of m...

Page 5: ...EST SWITCH 3 6 5 4 RA 914 REMOTE LED TEST SWITCH 3 6 5 4 END OF PANEL LINE DEVICE CIRCUIT Figure 3 Detector Using 2 Wire 2WRLT Base with Remote Indicator and Remote Test Switch Optio FIRST DETECTOR BASE LAST DETECTOR BASE AUX RELAY AUX AUX RELA RELAY Y RA 914 CONTACTS RA 914 RA 914 CONT CONTACTS ACTS REMOTE LED FORM C REMOTE REMOTE LED LED FORM FORM C C TO CONTROL PANEL INITIATING CIRCUIT 8 7 3 6 ...

Page 6: ... been activated insert a smal screwdriver into the slot on the base to push the plastic tab while simultaneously turning the detector head counterclockwise see Figure 6 Use small bladed screwdriver 1 to push locking tab Test magnet 4 position 7 5 BREAK PLASTIC TAB BY TWISTING TOWARD CENTER OF BASE 1 BODY 2 CONTACT ARM 3 2 6 3 CONTACT SPRING 4 TERMINAL PLATE 5 JUMPER WIRE remove before installation...

Page 7: ...ING FENWAL SERIES 70 201000 XXX BASE RETROFIT ADAPTER MA 001 P N 70 501000 003 CPD 705x PSD 715x THD 705x Figure 8 Installing Mechanical Adapter MA 00 DETECTOR TESTING AND SENSITIVITY METERIN FREQUENC Testing shall be performed upon installation of the detector and once a year thereafter as stated in NFPA 72 latest edition Smoke Detector sensitivit shall be metered within one year of installation ...

Page 8: ... should alarm as indicated by stead illumination of the alarm indicator LEDs To return each detector to normal operation reset the control unit 4 Failure to alarm in test 3 indicates a defective detector requiring service 5 After taking appropriate corrective action re engage Alarm Signal Devices Releasing Devices and Extinguishing Systems and ensure that th entire system is returned back to norma...

Page 9: ...y Module 70 500000 102 4WRM Spare 4 Wire Relay Module DETECTOR ACCESSORIE Part No Model Description 06 117883 001 Test Magnet 29 116788 001 EOL Supervisory Relay 70 200000 911 RA 911 Remote Alarm Indicator 70 200000 914 RA 914 Remote Alarm Indicator w Smoke Detector Test Switch 70 500000 002 ST 001 Smoke Detector Sensitivity Tester 70 500000 003 DST 003 Wireless Infrared Smoke Detector Sensitivity...

Reviews: