background image

As per UL 521 Section 55.2, in order to minimize the possibility of false alarms, detectors shall not be mounted in a location where the thermal air path

to it may be obstructed. For additional information, consult the Fenwal Automatic Fire Detection Application Engineering Manual MC-402, NFPA-72

and the local AHJ.

Mounting

Bases are mounted directly on the electrical junction boxes (3, 3.5, and 4 inch octagonal; 3 inch round; 4 inch square) without any type of mechanical

adapter.
SMOKE DETECTORS - DUCT APPLICATIONS

General

The NFPA states that Duct Smoke Detectors must not be used as a substitute for open area protection. Duct detection is intended for use in the

control of air handling equipment for the purpose of closing dampers or shutting down of air handling units. A Model RA 914 Remote Test Station must

be used in conjunction with all detectors used in ducts. This limits the types of bases that may be used to the 2WRLT, 2WRB and 4WRB. See Figures

2 through 5 for wiring details.

Pre-installation Rules

Fenwal recommends actual measurements of the air flows and examination of engineering specifications that define expected velocities in all models

of equipment used to determine if a location is suitable for air duct detection operation. An Alnor Instrument Co., Chicago, IL Model 6000P Velometer,

or equivalent may be used to check the duct air velocity.

Air Velocities

Velocity Ratings of Detectors when used for In-Duct applications are as follows:

Model 

In-Duct (fpm) 

Model 

In-Duct (fpm) 

CPD-7051 

500 - 2000 

PSD-7155P 

500 - 4000 

CPD-7051D 

500 - 2000 

PSD-7155D 

500 - 4000 

Installation Rules

1.

Refer to NFPA 72 Appendix-A for detector installation requirements.

2.Locate Detectors approximately 6-duct widths downstream from bends or inlets.

 These locations are fairly uniform in non-turbulent airflow and

homogenous with respect to air/smoke mixing.

Exception

: Where it is physically impossible to locate the detector accordingly, the detector can be positioned closer than 6-duct

widths, but as far as possible from the opening, bend or deflection plates.

3

.

Locate duct detectors so that dampers do not restrict air flow at the detector location.

4.Locate air duct detectors on the return duct of the equipment’s air handling system.

 However, detectors should not be installed in the return air

damper branch.

5.Locate detectors on branch lines if close identification of the source of alarm is required.

6.Locate detectors on the downstream side of filters to sense fires in the filters.

 However, it should be noted that should the filters block the air

flow, sufficient air flow may no longer be present for proper operation of the duct detector.

7.Locate detectors, whenever possible, where they can be conveniently observed and readily serviced.

8.Locate detectors in return air ducts ahead of mixing areas.

9.Do not locate detectors immediately following outside air inlets except to monitor smoke entry to the handling system from an adjacent area.

10.When possible, locate detectors upstream of air humidifiers and downstream of dehumidifiers.

INSTALLATION AND WIRING NOTES AND CAUTIONS
1.To ensure proper installation of the detector head to the base, be sure wires are properly dressed at installation.

 Position all wires flat against the

base. Take all slack in the outlet box. Route wires away from connector terminals.

2.If the supplied jumper wire has been installed between terminals 6 and 7 (by inserting the jumper into the holes provided in the contact blades of

terminals 6 and 7) to test detector loop continuity, be sure to remove the jumper before installing the detector head.

3.Do not loop wire under Terminal 1.

 Break wire run to provide supervision of connections.

4.Observe detector polarity when using LED return wire and when using Remote Test option.

5.All relays are shown in normal position (POWER ON).

 Ratings of Auxiliary contacts are as specified in DETECTOR BASES.

6.The end-of-line supervisory device shall be compatible with the control unit used.

 The end-of-line supervisory relay utilized shall be and rated for

the DC supply voltage used. The Fenwal end of line relay P/N 29-116788-001 is rated for 24 VDC operation.

7.When detectors employ the 2WRB base with relay, all detectors on a loop must be equipped with this option and all must be interconnected to

perform a common function.

8.Model RA-911 P/N 70-200000-911 Remote LEDs can be installed with both Smoke (CPD & PSD) and Heat (THD) Detectors.
9.Model RA-914 P/N 70-200000-914 Remote Test Switches can be installed only with Smoke (CPD & PSD) Detectors.
10.Do not install detector heads until the area has been thoroughly cleaned of construction debris, dust, etc.

11. As per UL 268 Section 77.1.7, Smoke Detectors are not to be installed with detector guards unless the combination has been evaluated and

found suitable for that purpose.

WIRING DIAGRAMS

Figures 1, 2, 3 and 4 are typical wiring diagrams of 2-Wire Detector systems and Figure 5 shows a 4-Wire detector system (field wiring is shown
dashed).

Summary of Contents for PSD Series

Page 1: ...www fenwal direct eu www prevent a fire eu Smoke Detector PSD 2 4 Wire Units ...

Page 2: ...re detection feature rated at 15 F 8 3 C per minute All detectors are designed for 2 Wire and 4 Wire installation using the appropriate Detector bases The Smoke and Heat Detectors are UL Listed fo Open Area Protection applications per UL 268 and UL 521 respectively Detectors may also be installed in systems intended for Releasing Devic Service through use of a compatible Fire Alarm Control Panel D...

Page 3: ...iling obstructions high air exchange rates etc reduced spacing must be used to achieve adequat protection Computer rooms and other such installations may require spacing with a maximum of 200 square feet 18 6 m2 due to high air exchang rates For additional information consult NFPA 72 and the Fenwal Automatic Fire Detection Application Engineering Manual MC 402 Per UL Listing open area smoke detect...

Page 4: ...m is required 6 Locate detectors on the downstream side of filters to sense fires in the filters However it should be noted that should the filters block the ai flow sufficient air flow may no longer be present for proper operation of the duct detector 7 Locate detectors whenever possible where they can be conveniently observed and readily serviced 8 Locate detectors in return air ducts ahead of m...

Page 5: ...EST SWITCH 3 6 5 4 RA 914 REMOTE LED TEST SWITCH 3 6 5 4 END OF PANEL LINE DEVICE CIRCUIT Figure 3 Detector Using 2 Wire 2WRLT Base with Remote Indicator and Remote Test Switch Optio FIRST DETECTOR BASE LAST DETECTOR BASE AUX RELAY AUX AUX RELA RELAY Y RA 914 CONTACTS RA 914 RA 914 CONT CONTACTS ACTS REMOTE LED FORM C REMOTE REMOTE LED LED FORM FORM C C TO CONTROL PANEL INITIATING CIRCUIT 8 7 3 6 ...

Page 6: ... been activated insert a smal screwdriver into the slot on the base to push the plastic tab while simultaneously turning the detector head counterclockwise see Figure 6 Use small bladed screwdriver 1 to push locking tab Test magnet 4 position 7 5 BREAK PLASTIC TAB BY TWISTING TOWARD CENTER OF BASE 1 BODY 2 CONTACT ARM 3 2 6 3 CONTACT SPRING 4 TERMINAL PLATE 5 JUMPER WIRE remove before installation...

Page 7: ...ING FENWAL SERIES 70 201000 XXX BASE RETROFIT ADAPTER MA 001 P N 70 501000 003 CPD 705x PSD 715x THD 705x Figure 8 Installing Mechanical Adapter MA 00 DETECTOR TESTING AND SENSITIVITY METERIN FREQUENC Testing shall be performed upon installation of the detector and once a year thereafter as stated in NFPA 72 latest edition Smoke Detector sensitivit shall be metered within one year of installation ...

Page 8: ... should alarm as indicated by stead illumination of the alarm indicator LEDs To return each detector to normal operation reset the control unit 4 Failure to alarm in test 3 indicates a defective detector requiring service 5 After taking appropriate corrective action re engage Alarm Signal Devices Releasing Devices and Extinguishing Systems and ensure that th entire system is returned back to norma...

Page 9: ...y Module 70 500000 102 4WRM Spare 4 Wire Relay Module DETECTOR ACCESSORIE Part No Model Description 06 117883 001 Test Magnet 29 116788 001 EOL Supervisory Relay 70 200000 911 RA 911 Remote Alarm Indicator 70 200000 914 RA 914 Remote Alarm Indicator w Smoke Detector Test Switch 70 500000 002 ST 001 Smoke Detector Sensitivity Tester 70 500000 003 DST 003 Wireless Infrared Smoke Detector Sensitivity...

Reviews: