background image

RATINGS

The ratings for the detector bases are provided in the following table; the UL Compatibility Identifier Number is listed in the CID column.

Detector 

Base Model or 
P/N 

CID 

Standby Voltage 
(VDC) 

Max. Alarm 
Current (mA) 

Max. Standby 
Current (µA) 

Typical Standby 

Current (µA) 

All Models 

2-WIRE 

FE51A 

10.2 - 36.8 

100 

70 

55 

2WRLT 

FE52A 

10.2 - 36.8 

100 

70 

55 

2WRB 

FE53A 

11.4 - 35.0 

100 

70 

55 

2WRB w/ LED 

FE55A 

11.4 - 35.0 

100 

70 

55 

4WRB 

N/A 

16.3 - 30.8 

100 

70 

55 

All models 

with MA-001 

Mechanical 

Adapter Base 

70-201000-001 

FE01A 

11.4 - 33.5 

100 

70 

55 

70-201000-002 

FE02A 

11.4 - 33.5 

100 

70 

55 

70-201000-003 

FE03A 

11.4 - 33.5 

100 

70 

55 

70-201000-005 

FE05A 

11.4 - 33.5 

100 

70 

55 

Note

:  Minimum Alarm Impedance = 195 ohms;  Maximum Alarm Impedance = 630 ohms. 

CONTROL UNIT SELECTION

For a complete list of UL Compatible Listed Control Panels refer Document No. 70.63 Detector-Control Panel Compatibility Listing. As per UL 268

Section 77.3.1(d) and UL 521 Section 54.3.1(d), this document also lists the maximum number of detectors that can be connected to each initiating

device circuit of the control unit. This includes any detectors that employ an integral component, such as a relay or sounder that consumes power

during an alarm condition.

DETECTOR INSTALLATION

SMOKE DETECTORS - OPEN AREA APPLICATIONS

Spacing

Smoke Detectors are UL Listed to be installed on maximum 30 foot (9.1 m) centers, typically on smooth ceilings up to 15 feet (4.6 m) high and will

operate with minimum air circulation. Resultant maximum 900 square foot (83.6 m

2

) spacing may be used as a reasonable guide for comparable

applications. Where special conditions exist (ceiling obstructions, high air exchange rates, etc.), reduced spacing must be used to achieve adequate

protection. Computer rooms and other such installations may require spacing with a maximum of 200 square feet (18.6 m

2

) due to high air exchange

rates. For additional information, consult NFPA 72 and the Fenwal Automatic Fire Detection Application Engineering Manual MC-402.
Per UL Listing, open area smoke detectors are intended for mounting on a ceiling not less than 6 inches (152 mm) from a wall, or on a wall not less

than 4 inches (102 mm) nor more than 6 inches (152 mm) from the ceiling.
The following locations should always be avoided: areas with excessive exhaust fumes, kitchen areas, near fireplaces or furnace rooms, within three

(3) feet of air supply ducts or air diffusers.

Air Velocities

Velocity Ratings of Detectors when used for Open Area protection are as follows:

Model 

Open Area (fpm) 

Model 

Open Area (fpm) 

CPD-7051 

0 - 300 

PSD-7155P 

0 - 4000 

CPD-7051D 

0 - 300 

PSD-7155D 

0 - 300 

CPD-7054 

0 - 300 

PSD-7156 

0 - 300 

CPD-7054D 

0 - 500 

PSD-7157 

0 - 300 

PSD-7155 

0 - 300 

PSD-7157D 

0 - 4000 

Mounting

Bases are mounted directly on the electrical junction boxes (3, 3.5, and 4 inch octagonal; 3 inch round; 4 inch square) without any type of mechanical

adapter.
HEAT DETECTORS - OPEN AREA APPLICATIONS

Spacing

For UL/cUL applications, the Detectors are listed to be installed on 70 foot (21.3 m) centers, typically on smooth ceilings up to 15 feet (4.6 m) high and

will operate with minimum air circulation. Detectors are intended for mounting on a ceiling not less than 35 feet (10.7 m) from a wall or partition.
For FM applications, the listed spacing is 35 foot x 35 foot (10.7 m x 10.7 m). Where special conditions exist (ceiling obstructions, etc.), reduced

spacing must be used to achieve adequate protection.

 

www.fenwal-direct.eu

www.prevent-a-fire.eu 

Summary of Contents for PSD Series

Page 1: ...www fenwal direct eu www prevent a fire eu Smoke Detector PSD 2 4 Wire Units ...

Page 2: ...re detection feature rated at 15 F 8 3 C per minute All detectors are designed for 2 Wire and 4 Wire installation using the appropriate Detector bases The Smoke and Heat Detectors are UL Listed fo Open Area Protection applications per UL 268 and UL 521 respectively Detectors may also be installed in systems intended for Releasing Devic Service through use of a compatible Fire Alarm Control Panel D...

Page 3: ...iling obstructions high air exchange rates etc reduced spacing must be used to achieve adequat protection Computer rooms and other such installations may require spacing with a maximum of 200 square feet 18 6 m2 due to high air exchang rates For additional information consult NFPA 72 and the Fenwal Automatic Fire Detection Application Engineering Manual MC 402 Per UL Listing open area smoke detect...

Page 4: ...m is required 6 Locate detectors on the downstream side of filters to sense fires in the filters However it should be noted that should the filters block the ai flow sufficient air flow may no longer be present for proper operation of the duct detector 7 Locate detectors whenever possible where they can be conveniently observed and readily serviced 8 Locate detectors in return air ducts ahead of m...

Page 5: ...EST SWITCH 3 6 5 4 RA 914 REMOTE LED TEST SWITCH 3 6 5 4 END OF PANEL LINE DEVICE CIRCUIT Figure 3 Detector Using 2 Wire 2WRLT Base with Remote Indicator and Remote Test Switch Optio FIRST DETECTOR BASE LAST DETECTOR BASE AUX RELAY AUX AUX RELA RELAY Y RA 914 CONTACTS RA 914 RA 914 CONT CONTACTS ACTS REMOTE LED FORM C REMOTE REMOTE LED LED FORM FORM C C TO CONTROL PANEL INITIATING CIRCUIT 8 7 3 6 ...

Page 6: ... been activated insert a smal screwdriver into the slot on the base to push the plastic tab while simultaneously turning the detector head counterclockwise see Figure 6 Use small bladed screwdriver 1 to push locking tab Test magnet 4 position 7 5 BREAK PLASTIC TAB BY TWISTING TOWARD CENTER OF BASE 1 BODY 2 CONTACT ARM 3 2 6 3 CONTACT SPRING 4 TERMINAL PLATE 5 JUMPER WIRE remove before installation...

Page 7: ...ING FENWAL SERIES 70 201000 XXX BASE RETROFIT ADAPTER MA 001 P N 70 501000 003 CPD 705x PSD 715x THD 705x Figure 8 Installing Mechanical Adapter MA 00 DETECTOR TESTING AND SENSITIVITY METERIN FREQUENC Testing shall be performed upon installation of the detector and once a year thereafter as stated in NFPA 72 latest edition Smoke Detector sensitivit shall be metered within one year of installation ...

Page 8: ... should alarm as indicated by stead illumination of the alarm indicator LEDs To return each detector to normal operation reset the control unit 4 Failure to alarm in test 3 indicates a defective detector requiring service 5 After taking appropriate corrective action re engage Alarm Signal Devices Releasing Devices and Extinguishing Systems and ensure that th entire system is returned back to norma...

Page 9: ...y Module 70 500000 102 4WRM Spare 4 Wire Relay Module DETECTOR ACCESSORIE Part No Model Description 06 117883 001 Test Magnet 29 116788 001 EOL Supervisory Relay 70 200000 911 RA 911 Remote Alarm Indicator 70 200000 914 RA 914 Remote Alarm Indicator w Smoke Detector Test Switch 70 500000 002 ST 001 Smoke Detector Sensitivity Tester 70 500000 003 DST 003 Wireless Infrared Smoke Detector Sensitivity...

Reviews: