FEMA ELECTRÓNICA . Series K . K40-C1
14
1.19 Configuration menu (cont.)
The ‘
On Power Up
’ (‘
on.Pu
’) menu configures functions to apply at
start-up. It applies only to instrument restart after power loss. It does
not apply to instrument restart due to change in configuration.
• parameter ‘
Delay
’ (‘
dLAy
’) assigns a waiting time in seconds. The in-
strument waits the configured time before starting normal function.
During this waiting time, the display shows all decimal points on in
flash mode, all alarms are in ‘oFF’ state, there is no signal acquisition
and there is no communications or control being performed. After
the configured time is over, the instrument starts in normal function.
Application - the start-up process for an automation system implies
that different parts of the system (engines, actuators, controllers, ...)
have different start-up times. The ‘Delay’ function gives time to the
instrument to wait until the slowest part of the system is fully func-
tional before executing actions on the system (signal reading, relay
activation, ...)
• the ‘
Reset
’ (‘
rSt
’)
parameter will execute a reset of the counter
each time the instrument is restarted.
1.19.14 Menu ‘On Power Up’
Tools
Key UP
(‘fast access’)
Memory of
maximum
Memory of
minimum
Setpoint 1
Setpoint 2
Setpoint 3
Memory of
cycles
Preset value
On power-up
Delay
Seconds
Reset
The ‘UP’ (
5
) key at the front of the instrument gives access to a list
of functions configurable by the operator. See section 1.17 for an ex-
planation on how to operate the ‘
fast access
’ menu.
The ‘
Key UP (Fast access)
’ (‘
K.uP
’) menu allows to select which func-
tions will be accessible through the ‘fast access’ menu. Select ‘
on
’ to
activate each function.
• the ‘
Setpoint
1
’ (‘
ALr1
’) function allows to visualize and modify the
alarm
1 setpoint through the ‘fast access’ menu.
• the ‘
Setpoint
2
’ (‘
ALr2
’) function allows to visualize and modify the
alarm
2 setpoint through the ‘fast access’ menu.
• the ‘
Setpoint
3
’ (‘
ALr3
’) function allows to visualize and modify the
alarm
3 setpoint through the ‘fast access’ menu.
• the ‘
Memory of maximum
’ (‘
MAX
’)
or
‘
Memory of minimum
’
(‘
MIn
’) functions allow to visualize the maximum or minimum read-
ing value stored in memory. To reset this value, visualize the memory
value at the ‘fast access’ menu with key UP (
5
) and when message
‘
rSt
’ is displayed, press (
<
) to reset.
• the ‘
Memory of cycles
’ (‘
cYcL
’)
function allow to visualize and reset
the memory of cycles. To reset this value, visualize the memory value
at the ‘fast access’ menu with key UP (
5
) and when message ‘
rSt
’
is displayed, press (
<
) to reset. The memory of cycles countes ‘+1’
each time a reset alarm occurs (‘on_AL’ / ‘to_0’ or ‘to_P’) or a reset
by ‘overrange’ / ‘underrange’ occurs.
• the ‘
Preset value
’ (‘
PrSt
’)
function allows to visualize and modify
the preset value configured.
1.19.12 Fast access
If only a single function is selected for the ‘fast access’ menu, press-
ing the the ‘UP’ (
5
) key will shortly display the function name and
then automatically jump to the function value.
1.19.13 Super fast access