![Federal 90 Series Troubleshooting Manual Download Page 39](http://html1.mh-extra.com/html/federal/90-series/90-series_troubleshooting-manual_3787664039.webp)
CONDITION
Water On The Floor
Caution!
Water on flooring can not only cause damage, but can also create
a slip hazard. Until properly diagnosed and repaired, be sure to follow these
procedures:
•
Use of a wet-dry shop vacuum is recommended to remove excess water
from both the floor and condensate pan as well as the interior of the unit’s
base.
•
Water in the condensate pan may be extremely hot if the pan is working
properly and cannot keep up.
Personal Protection Equipment such as gloves
and long sleeves must be used when emptying the condensate pan to avoid
injury.
Caution!
During a power failure, the condensate pan may overflow and
cause damage and a slip hazard! Restore power as soon as possible. Until
such time that power is restored, follow the steps above.
Display Cases
are subject to air disturbance and due to direct sunlight and
close proximity of heating ducts, grills, radiators, ceiling fans or main doors.
Also avoid locations where the unit is subject to high humidity such as near
cases with water misting or fogging devices.
Check Ambient Conditions of the Location
Most of our cases require a maximum ambient of 75°Farenheit / 55% RH
(Relative Humidity) Exceeding either or both can result in the condensate pan
overflowing.
Check that the drain trap assembly did not become dislodged during shipment
or installation and that it is correctly positioned over condensate pan, pump, or
floor drain.
Check that the drain trap is free of debris such as algae, food product and
packaging.
Condensate Pan Assemblies with Float
If equipped, check condensate pan float, if applicable for proper operation. If
the float is not floating, clean the pan and float of debris to see if it will float, if
not, replace the condensate pan assembly.
NOTE: Parts for condensate pans starting with SA, parts are available.
WATER ON FLOOR
MARKET SERIES
COLD DELI & COLD BAKERY
38