No Power

Check that the master power switch is on. (located next to the Carel

Controller)

Carel Electronic Thermostat

(located behind lift up cover) 

above the light switch on the top 

of the base of the unit.)

Check to see that the control is turned on.

Control Display Is Flashing - 

If the control is flashing all of its lights, it is 

likely that you have a grounding issue with the power source.  Verify that 

the unit is properly grounded.

Check to see if the compressor run indicator is on, calling for cooling.

Defrost Mode

Is the unit entering into defrost too often, or staying in defrost to long? Our 

cases typically defrost every 6 to 8 hours as long as the evaporator sensor 

is below defrost termination temperature of approximately 43°F. There is 

also a defrost on demand feature that can supersede the normal defrost 

interval as

needed. – 30 minute maximum, defrost duration.

Check Set Point Temperature; it # 1 is the warmest and # 9 is the coldest – 

set typically between 4 & 5 – adjust accordingly – control has a minimum 

run time of 5 minutes and a maximum run of 75 minutes (self-contained 

units) and 60 minutes (remote condensing unit).

Supply Air Temperature – Press & Hold Down (Defrost) immediately 

followed by Up (Power) – You must keep them both held to see the 

temperature.

Check the return air grill inside unit for obstructions.

Check that the top air discharge diffuser is not blocked with dust or debris. 

The airflow should be approximately 200 fpm.

Check that the condenser air inlet and condenser air outlet are not

restricted.

Check that all evaporator fan motor and blades are working as they should.

Check that the condenser fan motor and blade are working as they should.

Check that the evaporator is clear and not obstructed with ice or debris

Check TXV bulb installation is secure and insulated.

Check that superheat is between 8°F to 12°F

.

If equipped, check sight glass for flashing and/or low charge.

Compressor Is Not

Operating

Check the electronic temperature control to see if the unit has the

compressor indicator illuminated.

19

Summary of Contents for 90 Series

Page 1: ...S Italian Glass New Bakery Series 90 ITR ITG CGR SGR SN Market Series SQ RSSM NSSM RSSD RSSL 28 29 Water on the Floor 30 31 32 33 Stand Alone RSS and Hybrid CD RSS RSS Confection FCC FCCR 34 35 38 40...

Page 2: ...the decorative back panel during transit Check that the light switch is on Shelf lights lamp cord must be fully seated into receptacle gently tap them in with a rubber mallet if needed to make full c...

Page 3: ...es and condensing unit for vibration Check compressor for any abnormal noises Lights Not Working Check that the light switch is on Shelf lights lamp cord must be fully seated into receptacle gently ta...

Page 4: ...light switch is on Shelf lights lamp cord must be fully seated into receptacle gently tap them in with a rubber mallet if needed to make full contact Check that the lamp cord is plugged into the end...

Page 5: ...on Check compressor for any abnormal noises Lights Not Working Check that the light switch is on Shelf lights lamp cord must be fully seated into receptacle gently tap them in with a rubber mallet if...

Page 6: ...e LED light strip Replace light if necessary Check power AC input voltage at LED driver Check to DC output voltage at LED driver If no output disconnect output from unit wiring harness and try again a...

Page 7: ...rd is plugged into the end of the LED light strip Replace light if necessary Check power AC input voltage at LED driver Check to DC output voltage at LED driver If no output disconnect output from uni...

Page 8: ...n Check compressor for any abnormal noises Lights Not Working Check that the light switch is on Shelf lights lamp cord must be fully seated into receptacle gently tap them in with a rubber mallet if n...

Page 9: ...acle gently tap them in with a rubber mallet if needed to make full contact Check that the lamp cord is plugged into the end of the LED light strip Replace light if necessary Check power AC input volt...

Page 10: ...both can result in temperature issues as the evaporator coil ices up and restricts airflow Check that the condenser air inlet and outlet are not restricted If equipped check condenser coil filter is...

Page 11: ...maximum defrost duration as well as a 30 minute minimum between defrosts Freezing Product Adjust temperature control to a warmer set point 1 Warmest 9 Coldest For electronic control only verify 10KOh...

Page 12: ...frigerant is not overcharged Check the sub cooling Check that the service valves are fully open Head Pressure Too Low Check unit for refrigerant leaks Perform pump down procedure to verify the valves...

Page 13: ...fied 230V DO NOT CONVERT TO LED BULBS AS THE CASE WILL NOT REACH TEMPERATURE Unit must be preheated prior to placing product into case Product temperature entering the case has to be at least 170 F or...

Page 14: ...Food Too Warm Adjust thermostat to a cooler setting outside of peak serving periods while maintaining proper product temperature REFER TO THE OWNER S MANUAL FOR MORE DETAIL 13...

Page 15: ...t the condenser coil is clean Warm Product Check that thermostat is on Check for proper power at the compressor Adjust thermostat accordingly the coldest setting is 9 Check TXV bulb installation is se...

Page 16: ...r refrigerant leaks Perform pump down procedure to verify the valves are pumping If equipped check if sight glass is flashing or showing low charge Low Suction Pressure Check unit for refrigerant leak...

Page 17: ...ait 10 seconds and power the unit back on If error is still present ensure all heater cords are fully seated into their receptacles Verifying Shelf Temperature On Controller To Temporarily See the Cur...

Page 18: ...60 KOhm sensor chart Temperature Is Too High Decrease control set point Check the control for errors and contact service Use supplied food rack to reduce heat intensity on food Ohm out probe to verify...

Page 19: ...ate a wall all of the way around the shelves to create a barrier keeping the cold air inside of the unit The product should be a minimum of half an inch off the tower to allow supply air to circulate...

Page 20: ...armest and 9 is the coldest set typically between 4 5 adjust accordingly control has a minimum run time of 5 minutes and a maximum run of 75 minutes self contained units and 60 minutes remote condensi...

Page 21: ...e service valves are fully open Head Pressure Too Low If equipped check the sight glass for flashing Check unit for refrigerant leaks Perform pump down procedure to verify the valves are pumping Low S...

Page 22: ...condenser coil is clean Non refrigerated cases do not regulate internal temperature and may be slightly higher than ambient temperature due to lighting in the unit or direct sunlight Mechanical Thermo...

Page 23: ...eck is the cold zone Cold Zone only 7 of the interior floor near the rear of the case and extends down to 3 at the front of the case by the customer Products above this load line will be in an unsafe...

Page 24: ...has its own mechanical thermostat which can be turned off and adjusted individually Each food well has its own mechanical thermostat which will control them individually Check that the slots along th...

Page 25: ...and restricts airflow Check that the condenser coil is clean Non refrigerated cases do not regulate internal temperature and may be slightly higher than ambient temperature due to lighting in the uni...

Page 26: ...Products above this load line will be in an unsafe temperature zone and disrupt the cold zone causing it to struggle as well Verify 10KOhm NTC sensor is reading properly Check that the condenser air i...

Page 27: ...to be operated with the rear doors in place but they may be removed during peak times The display will not read accurately with the rear doors removed for extended periods of time Food In Well Not Hel...

Page 28: ...is working Check the placement of the humidity pan which is located underneath the interior display deck for proper positioning or potentially missing from being removed during cleaning Check the flo...

Page 29: ...circulate and not freeze product at the back wall Some items may need more clearance if they are sensitive to freezing as supply air temperature should get below freezing If equipped check that conden...

Page 30: ...mpressor from engaging even if the electronic unit controller is calling due to low charge Check for power in and out of pressure control as both Low and High side pressure cutout will keep compressor...

Page 31: ...ans or main doors Also avoid locations where the unit is subject to high humidity such as near cases with water misting or fogging devices Check Ambient Conditions of the Location Most of our cases re...

Page 32: ...tank by pushing tabs located on tank sides away from the deck while lifting on pump cover Periodically inspect the condensate pump tank to assure it is free of accumulated dirt or sludge DO NOT use so...

Page 33: ...ity of heating ducts grills radiators ceiling fans or main doors Also avoid locations where the unit is subject to high humidity such as near casesn with water misting or fogging devices Check Ambient...

Page 34: ...d on tank sides away from the deck while lifting on pump cover Periodically inspect the condensate pump tank to assure it is free of accumulated dirt or sludge DO NOT use solvent cleaners Clean tank w...

Page 35: ...t is subject to high humidity such as near cases with water misting or fogging devices Check that the drain trap s assembly did not become dislodged during shipment or installation and that it is corr...

Page 36: ...may be removed for cleaning or replacement by unscrewing with a 9 16 wrench Clean Inlet and outlet piping Reassemble system and check for correct operation Condensation On The Center Tower Check Ambie...

Page 37: ...ight and close proximity of heating ducts grills radiators ceiling fans or main doors Also avoid locations where the unit is subject to high humidity such as near cases with water misting or fogging d...

Page 38: ...re it is free of accumulated dirt or sludge DO NOT use solvent cleaners Clean tank with soap and warm water only Check valve may be removed for cleaning or replacement by unscrewing with a 9 16 wrench...

Page 39: ...nlight and close proximity of heating ducts grills radiators ceiling fans or main doors Also avoid locations where the unit is subject to high humidity such as near cases with water misting or fogging...

Page 40: ...l properly diagnosed and repaired be sure to follow these procedures Use of a wet dry shop vacuum is recommended to remove excess water from both the floor and condensate pan as well as the interior o...

Page 41: ...densing fogging the glass and running down and out the units drain The bucket needs to be emptied and cleaned as needed to avoid overflowing and or growth of mold Floor Drain Floor Drain Note Owner Re...

Page 42: ...proximity of heating ducts grills radiators ceiling fans or main doors Also avoid locations where the unit is subject to high humidity such as near cases with water misting or fogging devices Check A...

Page 43: ...lean the pan and float of debris to see if it will float if not replace the condensate pan float assembly and or heater accordingly If equipped check that condensate pan or pump is properly plugged in...