14
Informer Wall Mount Series
Installation Instructions
MERGEFORMAT
Configuring
the
Informer-IPFORMAT
General
Description
ations
3. Route the supply wires (10 AWG to 16 AWG) into the housing.
4. Strip a maximum of 0.28 inch (7 mm) of insulation from the ends of the power
leads. Coil any excess wire and secure under the terminal block to avoid contact
with other wiring and components.
5. Connect the wires to the terminal block by inserting the stripped ends of the wires
into the connectors as far as they can travel.
Connect the earth ground to the terminal block position G.
Connect the line (hot, L1) wire to position L.
Connect the neutral or the L2 wire to position N.
6. Tighten the clamping screw. The maximum tightening torque is 7.0 in-lb
(0.8 N • m).
7. Connect the earth ground to the terminal block.
8. Optional: If installing an LP1 strobe, do the following:
Find the loose wires for the LP1 strobe.
Attach the stripped black wire to the LP1 strobe negative (-) terminal.
Tighten the clamping screw. The maximum tightening torque is 7.0 in-lb (0.8
N • m).
Attach the red wire to the positive (+) terminal.
Run the wires thru the rubber gasket and thru the top of the Informer.
Attach the LP1 strobe to the top if the Informer using the LP1 supplied
hardware.
Attach the red and black wires to the connectors inside the Informer.
Summary of Contents for Informer I-HIOW
Page 29: ......