![FATEK FBs Series Manual Download Page 345](http://html1.mh-extra.com/html/fatek/fbs-series/fbs-series_manual_3764826345.webp)
Appendix -11
1.7
Special message display function
In general monitoring mode and soft key mode (16 KEYS or 8 KEYS), the user can configure the DAP to display
every kind of message under some circumstances, and the two-line display on the LCD can be controlled
separately to simultaneously display different messages. Every message is 1~511 words and numbers (ASCII code)
long, in which a maximum of 16 variables (if variables with 32-digit are not used, then it can use up to 25) can be
included. When a message has more than 16 words, the message will be displaced left for display, in which the
moving speed or pause time can be configured flexibly.
1.7.1
Message display application
The FB-DAPB(R) can be connected up to 16 sets (Number 1~16). Each DAP not only can display different
messages individually but make all the DAPs connected display the same message simultaneously. If you go to a
special contact (R3780~M3813) set by Enable, the DAP will display the message ASCII Code) indicated by the
corresponding indication register
(
R3780
~
M3813
)
. The content of the indication register is the start register of
messages, i.e. start of ASCII Code. The indication register content can be changed anytime in order to change and
display different messages.
The following is a list of corresponding special contacts and indication registers when each DAP is
displaying a message for control.
LCD line 1
LCD line 2
Number of
a message
displayed
Special
contact
Indication
register
Special
contact
Indication
register
1
~
16
M1800 R3780 M1801 R3781
1
M1802 R3782 M1803 R3783
2
M1804 R3784 M1805 R3785
3
M1806 R3786 M1807 R3787
4
M1808 R3788 M1809 R3789
5
M1810 R3790 M1811 R3791
6
M1812 R3792 M1813 R3793
7
M1814 R3794 M1815 R3795
8
M1816 R3796 M1817 R3797
9
M1818 R3798 M1819 R3799
10
M1820 R3800 M1821 R3801
11
M1822 R3802 M1823 R3803
12
M1824 R3804 M1825 R3805
13
M1826 R3806 M1827 R3807
14
M1828 R3808 M1829 R3809
15
M1830 R3810 M1831 R3811
16
M1832 R3812 M1833 R3813
※
The start register of a message
indicated by an indication register
means
:
0
~
8070
:
indicating R0
~
R8070
10000
~
13070
:
indicating D0
~
D3070
※
Special contacts M1800 and M1801
have a priority display function.
※
M1911 can control an alarm buzzer
whether to sound or not. If M1911=0
(
preset
)
, it shall be activated.
〈
Example
〉
Assume M1803 from 0
→
1, R3783=100
Result
:
Line 2 of No. 1 of the LCD will display messages in ASCII Code with R100 start.
〈
Example
〉
Assume M1828 from 0
→
1, R3808=10000
Result
:
Line 1 of No. 14 of the LCD will display messages in ASCII Code with D0 start.
〈
Example
〉
Assume M1801 from 0
→
1, R3781=0
Result
:
Line 2 of all the DAPs will display messages in ASCII Code with R0 start.