![FATEK FBs Series Manual Download Page 341](http://html1.mh-extra.com/html/fatek/fbs-series/fbs-series_manual_3764826341.webp)
Appendix -7
z
FUN
6
(
DEFINE SOFTKEY
-
8 KEYS
):
Self-defining 8 soft keys
FUN 7
(
ENTER SOFTKEY MODE
-
8 KEYS
):
Enter 8 soft key mode
1. Can self-define 8 soft keys
:
、
、
、
、
、
、
、
2. Definable
range
:
R0
~
R3839
、
D0
~
D2943
、
M0
~
M1899.
3. In defining M0
~
M1899, this key can be defined as one of the 5 modes.
Mode
Definition
Description
0 Set
(
S
)
Set this contact to 1
1 Reset
(
R
)
Set this contact to 0
2 Moment
(
M
)
1 in pressing, 0 in being released
3 Inverse
(
I
)
Pressing once will have one inverse phase.
4 Monitor
(
V
)
Monitor this contact
【
Example
】
Assume
definition as R0,
definition as M0 mode 0(Set). Once enter the 8 soft key
mode in function 7,
Then pressing
Ö
display address or DOC of R0.
Ö
display address or DOC of M0 and force M0 ON
Note 1
:
After defining the 8 soft keys, once function 7 is executed, it will enter 8 soft key operation mode.
And then the 8 soft keys will be executed according to function 6 definitions.
Note 2
:
、
both are allowed out of definition, but the other keys will not be effected without
definition.
Note 3
:
To return to normal operation mode, press
〝
+
(
D2972 content
)
+
〞
, among which
D2972 content is from 0000
~
9999
(
4 digits required
)
.
z
FUN
8
(
DEFINE SOFTKEY
-
16 KEYS
):
Self-define 16 soft keys
FUN 9
(
ENTER SOFTKEY MODE
-
16 KEYS
):
Enter 16 soft key mode
1. Available for defining 16 soft keys
:
、
、
、
、
、
、
~
2. Definable
range
:
T0
~
T255
、
C0
~
C199
、
R0
~
R3839
、
D0
~
D2943
、
M0
~
M1899
。
3. In defining M0
~
M1899, this key can be defined as one of the 5 modes and when a message is being
displayed, if the key is pressed, the display will not be changed.
Mode
Definition
Description
0 Set
(
S
)
Set this contact to 1
1 Reset
(
R
)
Set this contact to 0
2 Moment
(
M
)
1 in pressing, 0 in being released
3 Inverse
(
I
)
Pressing once will have one inverse phase.
4 Monitor
(
V
)
Monitor this contact
4. When defined as T, C, R or D, the value change is by pressing
or
to make the corresponding
M1840
~
M1871 ON (the client is required to write a plus/minus 1 program in the LADDER program) to achieve
this purpose.
Soft
key
0
1
2
3
4
5
6
7
8
9
T
C
D
R
SHIFT
×
M1840 M1841 M1842 M1843 M1844 M1845 M1846 M1847 M1848 M1849 M1850 M1851 M1852 M1853 M1854 M1855
Ø
M1856 M1857 M1858 M1859 M1860 M1861 M1862 M1863 M1864 M1865 M1866 M1867 M1868 M1869 M1870 M1871