2 -9
Register No.
Function
Description
R4010
│
R4011
Installed temperature sensor flag
Each bit represents 1 sensor,
if bit value = 1 means installed.
R4012
│
R4013
PID Temperature control flag
Each bit represents 1 temperature point, if bit value =
1 means enable control.
R4014 Reserved
R4015
Averaging of temperature value
=0, no average on temperature
=1, average by two readings
=2, average by four readings
=3, average by eight readings
=4, average by sixteen readings
R4016 Reserved
R4017 Reserved
R4018 Reserved
R4019 Reserved
R4020
│
R4024
Reserved
R4025
Total Expansion Input Registers
R4026
Total Expansion Output Registers
R4027
Total Expansion Digital Inputs
R4028
Total Expansion Digital Outputs
R4029 Reserved
for
system
R4030
│
R4039
Tables to save or read back the data
registers into or from ROM Pack
When the ROM Pack being used to save the ladder
program and data registers, these tables describes
which registers will be written into the ROM Pack.
The addressed registers will be initialized from ROM
Pack while power up.
R4040
Reply delay time settings for Port 0 and Port
1
Low Byte
:
For Port 0 (Unit in mS)
High Byte
:
For Port 1 (Unit in mS)
R4041
Reply delay time settings for Port 2 and Port
3
Low Byte
:
For Port 2 (Unit in mS)
High Byte
:
For Port 3 (Unit in mS)
R4042
Reply delay time settings for Port 4
Low Byte
:
For Port 4 (Unit in mS)
High Byte
:
Reserved for system
R4043
Port 3 Communication Parameters Register
Set Baud Rate, Data bit…of Port 3
R4044
Port 4 Communication Parameters Register
Set Baud Rate, Data bit…of Port 4
R4045
Transmission Delay & Receive
Time-out interval time Setting,
while Port 3 being used as the master of
FUN151 or FUN150
Low Byte
:
Port 3 Receive Time-out interval time
(Unit in 10mS)
High Byte
:
Port 3 Transmission Delay
(Unit in 10mS)