2 -8
2.4 Special Registers Details
Register No.
Function
Description
R3840
│
R3903
Input Registers
CH0 : R3840
│
│
CH63 : R3903
For Analog or Numeric inputs
R3904
│
R3967
Output Registers
CH0 : R3904
│
│
CH63 : R3967
For Analog or Numeric outputs
R3968
│
R3999
Raw Temperature Registers
TP0 : R3968
│
│
TP31 : R3999
For temperature measurement
R4000 Reserved
R4001 Reserved
R4002 Reserved
R4003 Reserved
R4004 Reserved
R4005 High
Byte
:
Period of PWM
=0, 2 seconds
=1, 4 seconds
=2, 8 seconds
=3, 1 second
=4, 16 seconds
≥
5, 32 seconds
Low Byte
:
Period of PID calculation
=0, 2 seconds
=1, 4 seconds
=2, 8 seconds
=3, 1 second
=4, 16 seconds
≥
5, 32 seconds
For PID temperature control
R4006
Threshold value of output ratio for
heating/cooling loop abnormal detecting (Unit
in %)
For PID temperature control
R4007
Threshold value of continuous time for
heating/cooling loop abnormal detecting (Unit
in second)
For PID temperature control
R4008
Maximum temperature for heating loop
abnormal detecting
For PID temperature control
R4009