
1 2 5 3 0 / 1 2 5 4 0 O W N E R ' S M A N U A L
P/N 447203 Issue I
VI-1
VI. PROGRAMMING THE CONTROL UNIT
MAIN TERMINATION BOARD JUMPERS
Factory setting is shown.
P12 – Processor Failure Relay Contact Type
•
DGRDO (Open – Form A)
•
•
DGRDC (Closed – Form B
P13 – External Power Monitor
•
On = Disabled
•
Off = Enabled
P50 – Addressable Device Circuit #1 Wiring Style
•
Style 4
•
•
Style 6/7
P51 – Addressable Device Circuit #2 Wiring Style
•
Style 4
•
•
Style 6/7
P52 – Reverse Polarity Supervision
•
Remote
•
•
Local
City Tie Selection Jumper Plug (Move the jumper plug to the desired type of city tie)
JP1 - Reverse Polarity
JP2 – Local Energy
JP3 – Shunt