FARADAY, LLC
447074 ISSUE I REV. C
PAGE 1 OF 2
INSTALLATION INSTRUCTIONS AND WIRING FOR
SERIAL ANNUNCIATOR UNIT
CAT. NO. SAU-1 P/N 12509 AND
SERIAL ANNUNCIATOR EXTENDER
CAT. NO. SAE-16 P/N 12510
The 12509 Annunciator Unit is an optional accessory for the 12100, 12120, 12500, 12530 or 12540 Fire
Alarm System Control Unit. The 12509 includes a processor board and an annunciator driver board. The
processor board receives commands from the control unit for activating the outputs and transmits
supervision and control functions to the control unit. The processor board can control up to 4 annunciator
driver boards. Each driver board provides 16 supervised outputs for LEDs or incandescent lamps. The
control unit can address up to 8 Serial Relay Units and/or Serial Annunciator Units. Auxiliary power
supplies will be required to power units beyond the control unit capability.
12509 PARTS SUPPLIED
1
413320
Processor Board Assembly
1
413322
Annunciator Driver Board Assembly
1
446653
34 pin Cable Assembly, 3 1/2”
1
447042
PCB Track, 14 1/2”
3
447080
10 pin Cable Assembly, 6”
2
18965
Keps Nut, #6-32
1
443269
Screwdriver
1
447074
Instruction Sheet
12510 PARTS SUPPLIED
1
413322
Annunciator Driver Board Assembly
1
446652
34 pin Cable Assembly, 15”
1
446653
34 pin Cable Assembly, 3 1/2”
1
447042
PCB Track, 14 1/2”
2
447080
10 pin Cable Assembly, 6”
2
18965
Keps Nut, #6-32
1
447074
Instruction Sheet
12509 DIMENSIONS
12510 DIMENSIONS
Step 1.) Installation is to be done by qualified personnel
who have thoroughly read and understood this
instruction sheet.
Step 2.) Disconnect all power into system, including
batteries.
Step 3.) Mount enclosure as required.
Note:
Enclosure must be UL Listed for Fire Protective
Signaling Use (Faraday P/N 401403 Fire Alarm
Accessory Enclosure).
Step 4.) Attach conduit and run wires as required.
Step 5.) Set processor board dip switch for proper
remote address (1- 8).
Step 6.) Set jumper P6 for desired buzzer operation.
J6 – BUZZER ACTIVATION
•
REMOTE
•
•
LOCAL
Step 7.) Mount PCB Track(s) using #6-32 keps nuts (P/N
18965) and snap in PCB assemblies.
Step 8.) Plug in the cable assembly(s) to the PCB
assemblies as required.
Step 9.) Connect IN wires from fire alarm system control
unit or previous remote as required.
Step 10.) Connect OUT wires to next remote or 120 ohm
terminating resistor (Faraday P/N 942664), if last
remote.
Step 11.) Connect LED’s or lamps, as required.
Step 12.) Apply power to system.
Step 13.) Program control unit for required annunciator
operation.
Step 14.) Check for proper operation of functions.