1 2 5 3 0 / 1 2 5 4 0 O W N E R ' S M A N U A L
P/N 447203 Issue I
II-9
GENERAL SPECIFICATIONS
Operating specifications for the 12530/12540 are as follows:
Environmental
•
Operating temperature
32 - 120
°
F (0 - 49
°
C)
•
Relative humidity
Up to 85% @ 86
°
F (30
°
C)
Primary Supply
•
Primary Input Voltage:
120 VAC (50/60 Hz) nominal (12530/12540-120)
240 VAC (50/60 Hz) nominal (12530/12540-240)
•
Maximum primary input current:
3.0A at 120 VAC
1.5A at 240 VAC
Secondary and Trouble Power Supply
•
24 volt lead-acid battery set:
•
Maximum Charge Voltage: 28.0 VDC
•
Maximum Charge Current: 2.75 A
•
Maximum Input Current: 4.66A
•
Battery capacity: 7-38 A.H. (over 10 A.H. requires separate enclosure)
Auxiliary Power Outputs
•
Current:
0.9 amp maximum for remote annunciators
0.9 amp maximum for auxiliary power outputs, DACT power and option boards
•
Non-Resettable Power Outputs
Power limited
Voltage: 24 VDC nominal
Ripple: 1.5 VAC maximum
•
Resettable Power Output
Power limited
Voltage: 24 VDC nominal
Ripple: 1.5 VAC maximum
Addressable Device Circuits
•
Power limited
•
Supervised
•
Voltage: 24 VDC nominal
•
Maximum Current (shorted): 0.25A
•
Maximum wire loop resistance: 20 ohms/line
Faraday Addressable Devices:
•
Two Style 4 or 6 circuits
•
Expandable to four Style 4 or 6 circuits with optional boards
•
60 detectors and modules max.
System Sensor Devices:
•
Two Style 4, 6 or 7 circuits
•
Expandable to four Style 4, 6 or 7 circuits with optional boards
•
99 sensors (smoke, heat) max
•
99 monitor and control modules max.