Installation
INSTAL
LAT
ION
Conn
ecti
on betwee
n mo
dul
es
8.
281
DDS
HARDWARE
Ref.1310
Ground connection
The chassis of each modules must be connected to a single point and from
there to the ground terminal of the electrical cabinet. When applying a 10 A
current between this ground point and any of these points, the voltage drop
must not exceed 1 V. Use the washers and nuts supplied with each module
to make the ground connection.
When not having a separate ground point, join the plates to the terminal of
the power supply module which, in turn, will be connected to mains ground.
The tightening torque must be between 2.3
2.8 Nm.
MANDATORY.
It is up to the system integrator to meet all the require-
ments of local and national electrical codes as well as all the regulations
applicable regarding the grounding of the whole unit.
F. H8/10
Ground connection.
MANDATORY.
Take a ground cable (as short as possible) from each mod-
ule to each main machine ground point.
MANDATORY.
In order to ensure compliance with the European Direc-
tive on Electromagnetic Compatibility 2004/108/EC, it is a must to:
•
Verify that all the requirements of local and national electrical codes are
met as well as all the regulations applicable regarding the grounding of
the whole unit.
•
Power the system through “MAINS FILTER
A”.
•
Secure the filter onto a metallic support with a good contact on its
whole base, good ground connection and as close to the power supply
as possible.
•
Make all the ground connections indicated in the figure
with a
cable having a section equal to or greater than the three-phase power
supply and at least 6 mm².
•
Always use shielded cables for three-phase motor connections. See
chapter
.
Summary of Contents for APS-24
Page 1: ...DRIVE DDS Hardware manual Ref 1310...
Page 6: ...I 6 DDS HARDWARE Ref 1310...
Page 9: ......
Page 10: ......
Page 11: ......
Page 12: ......
Page 16: ...16 Ref 1310 DDS HARDWARE...
Page 30: ...1 DESCRIPTION 30 Description DDS HARDWARE Ref 1310...
Page 94: ...2 POWER SUPPLIES 94 Power supplies DDS HARDWARE Ref 1310...
Page 188: ...3 DRIVE MODULES 188 Drive modules DDS HARDWARE Ref 1310...
Page 204: ...4 AUXILIARY MODULES 204 Auxiliary modules DDS HARDWARE Ref 1310...
Page 232: ...SELECTING CRITERIA 5 232 Selection criteria DDS HARDWARE Ref 1310...
Page 266: ...7 CABLES 266 Cables DDS HARDWARE Ref 1310...
Page 312: ...8 INSTALLATION 312 Installation DDS HARDWARE Ref 1310...
Page 326: ...9 FUNCTIONAL SAFETY 326 Functional safety DDS HARDWARE Ref 1310...
Page 354: ...10 CONNECTION DIAGRAMS 354 Connection diagrams DDS HARDWARE Ref 1310...
Page 378: ...12 SALES REFERENCES 378 Sales references DDS HARDWARE Ref 1310...
Page 384: ...13 COMPATIBILITY 384 Compatibility DDS HARDWARE Ref 1310...
Page 385: ......