ELECTRICAL WIRING DIAGRAM OF THE ELECTRONIC
PROGRAMMER

Once the connections have been made, do the first switching
test through the control panel. Set the motor run timer so that
the motor is allowed to run 4 - 5 seconds more than the gates.
Set the other timers to meet the site requirements. Set DIP
switch B No. 3 to 

automatic

 (ON): on pulsing to 4 - 8 the gates

must be operated as pre-set, ie. opening and only after the
dwell time, closing. Adjust the times through the respective
timers. (See No. 07, 08 and 09 drwg. No. 1643).
With DIP switch "B" No. 3 to 

semiautomatic

 (OFF) one pulse

opens the gates, a second pulse to 5 - 9 is needed to close
the gates. Any one pulse to 7 - 8 will open, close or reverse
the gates independently from the operation being performed.
It is recommended to carefully read the instructions in the
control box to have all the functions performed correctly.

The 6 LEDs on the P.C. board indicate the following:

Led No. 1 It switches on when voltage is supplied
Led No. 2 Photocells - Normally on. It switches off when the

photocells are obstructed

Led No. 3 Open - It switches on when the respective switch

is activated

Led No. 4 Close - It switches on when the respective switch

it activated

Led No. 5 Stop - Normally on. It switches off when the

respective switch is activated

Led No. 6 Radio - It switches on whenever a pulse is given,

either from remote control, keyswitch or push
buttons.

P.C. BOARD

CONNECTION DIAGRAM FOR SWING GATES

1 2 3 4 5

6 7 8 9 10 11 12 13 14 15

16 17 18

7    8

M1

M2

19 20 21 22 23 24 25

12,5

+

F

12,5

+

F

1

2

3

4

5

6

7

8

9

ON

OFF

1   2   3   4   5   6   7   8

ON

RADIO CONTROL

PLUG-IN CARD SUPPORT

ON TO “0” THE DELAY

IS OUT OF SERVICE

DWELL TIME

MOTOR RUN
OPEN & CLOSE TIME

CAPACITORS

MICROPROCESSOR

DIP-SWITCH

TERMINAL FOR
CONNECTIONS TO
PUSH BUTTONS PULIN 3

1 AMP. FUSE
24 V OUTPUT
TERMINALS 12-13

TIMER SWITCHES

FUSE

630 mA

FUSE 5 AMPS

1 st

 CHANNEL

24 V OUTPUT

Should more pairs of photocells be required

than the recommended quantity

, fit an auxiliary

transformer outside the control box.

= PHOTOCELLS 2

nd

 P

AIR =

Inside photocells N.C. cont

act

If obstructed they prevent the ga

tes from opening

reverse ga

te direction during close cycle

N.C. CONT

ACT

PHOTOCELLS

COMMON

OPEN SWITCH N.O. CONT

ACT

CLOSE SWITCH N.O. CONT

ACT

STOP SWITCH N.C. CONT

ACT

RADIO CONT

ACT N.O.

COMMON

VOL

TAGE OUTPUT

ELECTRIC LOCK SUPPL

Y

24 V INDICA

TOR - 3 W max.

24 V

OUTPUT A.C.

Max permitted load:

2 pairs photocells

1 radio receiver

COMMON

COMMON

230 V FLASHING LAMP

25 W max.

230 V SINGLE-PHASE

SUPPL

Y VOL

TAGE

ELECTRIC MOTORS
SINGLE-PHASE

NOTE WELL: For special applications, ie. to switch on lights -
CCTV etc., SOLID STATE RELAYS are recommended to be used
only. Standard relays would affect the micro-processor.

ALL OPERATIONS

OPEN, CLOSE AND

REVERSE

RADIO CONTACT

LEAF DELAY
TIMER CLOSE

LED No. 1 - It switches on when voltage is supplied

OPEN

STOP

CLOSE

N.O.

N.C.

N.O.

3

4

5

6

26 27 28 3

CONNECTION TO THE “PULIN 3” PUSH
BUTTONS WITH STATUS INDICATION LEDS.

0

FLASHING LAMP

630 mA FUSE

SAFETY CONT

ACT N.C.

3    4

NOTE WELL: THIS PANEL IS TESTED TO OPERATE GATES ONLY
THROUGH FADINI ACCESSORIES. NO WARRANTY IS
ACKNOWLEDGED BY THE MANUFACTURER IN CASE THAT
OTHER ACCESSORIES ARE USED OR NON CONFORMING
APPLICATIONS ARE MADE WITHOUT THE MANUFACTURER’S
APPROVAL.

+

+

+

26
27
28

PEDESTRIAN MODE
ONE PULSE OPENS
ONE GATE LEAF ONLY

PULSE TWICE CONSECUTIVELY

TO OPEN BOTH GATE LEAFS

II

12

3

4

ELECTRICAL CONNECTIONS
KEYSWITCH PRIT 19

STOP

OPEN

CLOSE

COMMON

TERMINAL BOARD

PRIT 19

1 2 3 4 5 6 7 8 9 10 11 12 13

TERMINAL BOARD

R

ADIO

CON

TA

C

T

S

T

OP N.C

.C

ON
TA

C

T

C

LOSE N.

O

.CON

TA

C

T

OPEN N.O

.CON

TA

C

T

COMMO

N

Summary of Contents for COMBI 740

Page 1: ...B Instruction manual COMBI 740 Oil hydraulic operator for swinging gates Below ground Version with two way locking device Version with brake in open close cycles Version with 110 and 175 shaft rotatio...

Page 2: ...RE VALVE CLOSE SAFETY PRESSURE VALVE OPEN VALVE COVER TWO WAY LOCKING VALVE ASSEMBLY MOTOR END PART MOTOR END PART PUMP SHAFT MOTOR BASE FLANGE SUCTION FILTER OIL RESERVOIR ELECTRIC MOTOR HYDRAULIC LO...

Page 3: ...IL RESERVOIR PLUG OIL RESERVOIR END CAP WIRE CONNECTORS HYDRAULIC OIL ARNICA A 15 BY AGIP ELECTRICAL CABLE RIGHT HAND JACK END CAP DAMPENING ADJUSTMENT ELBOW JOINT BEARING TOOTHED MAIN SHAFT CENTRAL B...

Page 4: ...6 LH 747 LH 746 RH 747 RH GATE SPACER HINGES NYLON WIRE It is recommended to keep to these instructions to install the equipment in the correct way to get a perfect working system Electro hydraulic op...

Page 5: ...close to the gate post dimensions as indicated in picture No 5 and lay the enclosure in it perfectly horizontal with the help of a level The upper edge of the enclosure must be levelled with the pavem...

Page 6: ...IN RELEASED POSITION OR NON LOCKING GATE FIXING PLATE WITH SHAFT FITTING COLLAR BOX SPANNER LONG BOLTS COMBI 740 SB RELEASE Once satisfied that everything has been done as described so far make sure...

Page 7: ...prevent misuse See pictures No 12 13 With single gates the electric lock is to be installed horizontally in the most suitable way to meet the application requirements Double gates can be fitted with a...

Page 8: ...AMPENING DAMPENING DEVICE OUT OF SERVICE IN SERVICE OIL FILLER CAP JUNCTION BOX CUT OUT BRICKWORK TO PROVIDE PROTECTION FOR THE CONTROL BOX Should the model with the dampening device be required to in...

Page 9: ...OR RUN OPEN CLOSE TIME CAPACITORS MICROPROCESSOR DIP SWITCH TERMINAL FOR CONNECTIONS TO PUSH BUTTONS PULIN 3 1 AMP FUSE 24 V OUTPUT TERMINALS 12 13 TIMER SWITCHES FUSE 630 mA FUSE 5 AMPS 1 st CHANNEL...

Page 10: ...Hz CONDENSER 12 5 F RED YELLOW GREEN BLUE RED CONNECT THE ENCLOSURE EARTH WIRE 2 1 3 10 PIC 21 PIC 20 SPECIAL VERSIONS FLOW REGULATORS FOR COMBI 740 MANUAL TEST FOR COMBI 740 ADJUSTMENT SCREW FLOW REG...

Page 11: ...HYDRAULIC PUMP Pump flow rate P3 0 85 l min Working pressure 1 MPa 10 bars Max pressure 3 MPa 30 bars Working temperature 20 C 80 C Rotation time 110 23 s Oil type A 15 FADINI by AGIP Shaft rotation a...

Page 12: ...TOTAL QUALITY CONTROL system which ensures constant quality standards updated knowledge of the European Standards and compliance with their requirements in view of an ever increasing process of impro...

Reviews: